HORIZONTAL EXAMPLES FOR COLINEAR DIRECT VENT

Max Vent Run - 40ft. Equivalent With Three (3) 90° Elbows

Special Note: The vent terminal 90° elbow and first 90° elbow off back of the heater, when within 6” (15.2cm), do not con- tribute to the overall vent length measurement. For each 45° elbow installed in the horizontal run, the length of the hori- zontal run MUST be reduced by 1.5 feet (45cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system. Reduce the length of the horizontal run 3 feet (91.4cm) for every 90° elbow.

Note: On horizontal runs, a P.V.C. support clamp needs to be in- stalled every 3 feet. No “sags” in horizontal vent runs; water will settle in the pipe.

When installing a colinear horizontal, the minimum vent length protruding from the outside wall is 6” (15.2cm) for air intake and 9” for exhaust. See Figure 27.

Note: Horizontal discharge 90° elbow must be pointed down- ward. See Figure 26. All horizontal runs require either a 1/4” per foot rise to run condensation back to the heater, or a 1/4” per foot downward slope to run condensation away from the heater.

Note: All PVC vent run piping can be purchased at a local hard- ware store. Schedule 40 PVC pipe should be used and cemented. PVCA Horizontal Colinear Direct Vent Adaptor, PVVTC Cap, PVVK-CFA Flex Kit and PVVK-SH Horizontal Vent Adaptor Kit are available from Empire Comfort Systems, Inc.

MIN. 2”

3” MIN.

6” MIN.

12” MIN.

9” MIN.

EXTERIOR GRADE

Figure 25

In both vertical and horizontal colinear direct vent applications, a colinear transition plate model PVCT can be used to minimize clearances between intake and exhaust pipes.

For horizontal colinear direct venting, exhaust and intake air, cap pipes with 90º elbows, pointed downward.

Figure 24

 

Note: If transition plate (model PVCT) is used, the measurement

 

for center to center of the pipes will be 2.5”. If the transition plate

 

(model PVCT) is not used, the measurement for center to center

 

of the pipes can be 3” to 24” maximum.

Figure 26

 

Note: Must maintain a minimum 3” between exhaust outlet and air intake.

Figure 27

Enhanced top view of Figure 26

Page 24

22618-12-0707

Page 24
Image 24
Elitegroup PV-28SV50-(BN,BP)-1, PV-28SV55-(CN,CP,GN,GP)-1 Horizontal Examples for Colinear Direct Vent