Transmitter Orientation and Power Supply
2.5.1DC power requirements for Model 2400S Analog and
If you are using DC power with a Model 2400S Analog or
•At startup, the transmitter power source must provide a minimum of 1 A of
•Length and conductor diameter of the power cable must be sized to provide 18 VDC minimum at the power terminals, at a load current of 0.5 A. To size the cable, refer to Table
MinimumSupplyVoltage = 18V + (CableResistance ⋅ CableLength ⋅ 0.5A)
Table
Gauge | Resistance(1) | |
14 AWG | 0.0050 | Ω/foot |
|
|
|
16 AWG | 0.0080 | Ω/foot |
|
|
|
18 AWG | 0.0128 | Ω/foot |
|
|
|
20 AWG | 0.0204 | Ω/foot |
|
|
|
2,5 mm2 | 0,0136 | Ω/meter |
|
|
|
1,5 mm2 | 0,0228 | Ω/meter |
|
|
|
1 mm2 | 0,0340 | Ω/meter |
|
|
|
0,75 mm2 | 0,0460 | Ω/meter |
|
|
|
0,5 mm2 | 0,0680 | Ω/meter |
|
|
|
(1) These values include the resistance of both high and low conductors in a cable.
Example The transmitter is mounted 350 feet from a DC power supply. If you want to use
16 AWG cable, calculate the required voltage at the DC power supply as follows:
MinimumSupplyVoltage = 18V + (CableResistance ⋅ CableLength ⋅ 0.5A)
MinimumSupplyVoltage = 18V + (0.0080 Ohms/ft ⋅ 350 ft ⋅ 0.5A)
MinimumSupplyVoltage = 19.4V
2.6Wiring the power supply
Note: This procedure is required only for Model 2400S Analog and
1.Remove the transmitter housing cover and user interface module as described in Section 2.4.
2.Unscrew the warning flap screw and raise the warning flap. Figure
3.Connect the power supply wires to terminals 9 and 10, as shown in Figure
4.Ground the power supply to the transmitter’s internal grounding screw, shown in Figure
5.Lower the warning flap and tighten the warning flap screw.
8 | Micro Motion® Model 2400S Transmitters |