Excessive current will damage the transmitter.

I/O Wiring – Model 2400S Analog Transmitters

Figure 3-2HART/analog single-loop wiring – Internal power

For analog communications:

820 Ohm maximum loop resistance

For HART communications:

600 Ohm maximum loop resistance

250 Ohm minimum loop resistance

HART-compatible

host or controller

+

Figure 3-3Basic mA output wiring – External power

 

 

 

VDC

 

+

 

 

 

Rload

+

Note: See Figure 3-5for voltage and resistance values.

Note: Channel B (terminals 3 and 4) can also be configured this way.

Manual backgroundManual backgroundManual background CAUTION

Excessive current will damage the transmitter.

Do not exceed 36 VDC input. Terminal current must be less than 500 mA.