Emerson 3000/ITR manual 3.1Features, 3.0OPERATION WITH ICOM CONTROL, Large and Small Displays

Models: 3000/ITR

1 72
Download 72 pages 16.82 Kb
Page 12
Image 12
3.0OPERATION WITH ICOM CONTROL

Operation with iCOM Control

3.0OPERATION WITH ICOM CONTROL

The Liebert iCOMcontrol offers the highest capabilities in unit control, communication and moni- toring of Liebert mission-critical cooling units.

Liebert iCOM may be used to combine multiple cooling units into a team that operates as a single entity, enhancing the already-high performance and efficiency of Liebert’s units.

3.1Features

Large and Small Displays

The Liebert iCOM control is available with either a large or small liquid crystal display.

The Liebert iCOM with small display has a 128 x 64 dot matrix screen that shows text and icons. This display is capable of controlling only the unit it is directly connected to.

The Liebert iCOM with large display has a 320 x 240 dot matrix screen that shows text and icons of 32 connected units (see Figure 4). This display can be used to control a single cooling unit or any cooling unit within a connected group over a network.

Liebert iCOM’s menu-driven display is used for all programming functions. The Status menu shows the temperature of the return or supply air and the and humidity of the return air.

Figure 1 Liebert iCOM components

Unit Panel Mount Large Display

Wall Mount Large DisplayUnit Panel Mountand Bezel

Small Display and Bezel

Liebert iCOM Input/Output Board

Liebert vNSA Network Switch

6