Component Operation and Maintenance
Manual
Valve Disassembly
1.Shut off the water supply by using isolating valves.
2.Relieve the tension on the main spring by turning the adjusting screw (or collar) as far as it will go (provide a container to catch water below the valve).
3.Remove four screws extending through the main spring housing.
4.Remove the center assembly screws for access to all internal parts.
5.Clean the seat if possible. If the seat is pitted or damaged, replace the valve rubber disc and valve seat.
6.After valve is reassembled check for leaks.
7.Readjust head pressure control.
Testing Function of
If the water continues to flow, the valve is either improperly adjusted (with head pressure too low) or the pressure sensing capillary is not connected properly to the condenser.
7.4.10Drycooler Settings
Applications with the Optional Stat Setting require field piping to be insulated to prevent condensa- tion. Table 8 shows acceptable applications where stats must be adjusted to Optional Setting. Aquastats must be
•GLYCOOL/Dual Cool applications
•Single Drycooler loops with motor ball valve flow controls (motor ball valves are used on all Lie- bert Challenger 3000 and ITR units with digital compressors).
Table 8 | Water/glycol system conditions requiring optional settings for aquastats |
| |||||||
Cooling Type |
| Glycool |
|
| Glycol |
| |||
|
|
|
|
|
|
|
| ||
Flow Control | MBV | WRV | MBV | WRV | |||||
|
|
|
|
|
|
|
|
| |
Drycoolers in Loop | 1 | Multiple | 1 | Multiple | 1 | Multiple | 1 | Multiple | |
|
|
|
|
|
|
|
|
| |
Stat Setting 1 | Optional | Optional | Optional | Optional | Optional | Factory | Factory | Factory | |
Insulate Field Piping | Yes | Yes | Yes | Yes | Yes | No | No | No | |
|
|
|
|
|
|
|
|
|
|
1.See Table 9.
2.MBV=motor ball valve; WRV=water regulating valve
Table 9 Aquastat
Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close
|
| Factory Setting | Optional Setting |
Aquastat # | Fans | (Glycol) (see Notes 1 and 2) | (GLYCOOL) (see Note 3) |
|
|
|
|
AQ1 | F1 | 65°F (18.3°C) | 35°F (1.7°C) |
|
|
|
|
AQ2 | F2 & F3 | 75°F (23.9°C) | 45°F (7.2°C) |
|
|
|
|
AQ3 | F4 | 70°F (21.1°C) | 40°F (4.4°C) |
|
|
|
|
NOTE
1. All drycoolers are shipped at Factory Setting.
2.Factory Setting is used for all glycol applications, except single drycooler loops with motor ball valve controls.
3.Stats must be
46