Component Operation and Maintenance

Replacing the Canister

Over a period of operation, the humidifier electrodes become coated with mineral solids. This coating insulates the electrodes and decreases the current flow. To maintain humidifier capacity, the water level slowly rises to expose fresh electrode. Eventually, the entire electrode becomes coated and the water level reaches the top. At this point, the canister full alarm is activated and the output begins to fall. When this happens, it is necessary to replace the full canister.

To replace the canister:

1.Turn the humidifier Off by lowering the humidity setpoint below the ambient humidity level. Record the original setpoint.

2.Place the RUN/DRAIN switch in the DRAIN position to drain the water from the canister.

3.Return the RUN/DRAIN switch to the RUN position after the canister has drained.

! WARNING

Risk of electric shock. Can cause injury or death.

To avoid a shock hazard, all power to the unit must be disconnected before proceeding with the canister replacement procedure.

4.Turn Off the power at the main unit.

5.Remove the cover from the humidifier cabinet.

! CAUTION

Risk of contact with hot surfaces. Can cause injury.

The canister and steam hose may be hot. Allow sufficient time for them to cool before working within the unit cabinet. Use extreme caution and wear protective gloves and arm protection when working on or near the canister or steam hose.

6.Locate the power wires to the steam canister. They are connected to the canister with 1/4" quick connects. Make note of the wiring configuration before removing any wires. Refer to the schematic on the unit. Slide the rubber boot back to expose the connections. Remove the three power wires and the two canister full wires. Do not loosen the screws that secure the electrodes.

7.Loosen the steam outlet hose clamp and slide the steam hose away from the canister top fitting.

8.The canister is now ready to be removed. Pull the canister straight up and out of the cabinet toward you.

9.Replace the canister with the part indicated in Table 11.

Table 11 Humidifier canister part numbers

Part

 

Capacity

Number

Voltage

lb/hr (kg/hr)

 

 

 

136798P1

200-460*

11 (5)

 

 

 

136798P2

380-575

11 (5)

 

 

 

* Can operate on 575V unit with transformer

10. Replace the canister by reversing the above procedure. Make special note of the following:

NOTE

When replacing the canister:

1.Make sure the two “O” rings are lubricated and properly seated on the bottom neck.

2.Always check the fill and drain solenoids for proper operation.

NOTE

When replacing the wiring, connect the red wire from Terminal #1 on the interface to the red top terminal on the canister. It is in the middle of a group of three terminals. The black wire from Terminal #2 on the interface connects to the power terminal farthest from the red terminal/wire. The power wire to this terminal is routed through the current sensing coil.

54

Page 60
Image 60
Emerson 3000/ITR manual Replacing the Canister, Humidifier canister part numbers, Part Capacity Number Voltage Lb/hr kg/hr

3000/ITR specifications

The Emerson 3000/ITR is a powerful and versatile instrument designed for industrial automation and process control applications. This modular platform integrates advanced features and technologies tailored to meet the needs of diverse industries including oil and gas, pharmaceuticals, and manufacturing.

One of the main features of the Emerson 3000/ITR is its exceptional scalability. The system can be easily expanded to accommodate growing operational demands. With its modular architecture, operators can add or remove components without significant downtime, ensuring continuous productivity. This flexibility allows businesses to adapt their systems to changing environments and requirements seamlessly.

The Emerson 3000/ITR leverages state-of-the-art communication technologies to ensure reliable data exchange between devices. With support for various protocols, including Hart, Modbus, and Profibus, the system can easily integrate with existing infrastructure. This adaptability enhances interoperability and simplifies the communication between field devices and control systems, promoting efficient data handling.

Built with robust security features, the Emerson 3000/ITR guarantees the integrity of sensitive data. The platform incorporates advanced encryption techniques and user authentication protocols to protect against potential cyber threats. This focus on security is essential in today’s digitally connected industrial environments.

Another key characteristic of the Emerson 3000/ITR is its user-friendly interface. The system is designed with operators in mind, featuring intuitive controls and comprehensive dashboards that provide real-time visibility into process performance. The graphical user interface simplifies complex operations, enabling quick decision-making and minimizing human errors.

Additionally, the Emerson 3000/ITR supports advanced analytics capabilities that enhance operational efficiency. By leveraging predictive analytics and machine learning algorithms, the system can identify patterns and anomalies, allowing for proactive maintenance and reducing the risk of unexpected downtime. This predictive maintenance approach helps organizations optimize their resources and extend the lifecycle of their equipment.

In conclusion, the Emerson 3000/ITR stands out as an exemplary solution for modern industrial automation. Its modular design, robust communication support, strong security measures, user-friendly interface, and advanced analytics capabilities make it an ideal choice for businesses looking to enhance their operational efficiency and adaptability. As industries continue to evolve, the Emerson 3000/ITR remains at the forefront, facilitating smarter and more efficient automation processes.