4.1.2Accessing Menus and Settings Viewing Data

Liebert iCOM Display Components and Functions

4.1.2Accessing Menus and Settings Viewing Data

No password is required to view data or settings. To view data:

1.From the home screen, press the Enter key to view the User Menu (see Figure 8).

2.Press Enter again to highlight the first icon.

3.Use the keyboard’s arrow keys to move to the icon for the data you wish to view.

4.Once that icon is highlighted, press Enter again to open that menu.

If a password is required, see 4.1.3 - Entering the Password.

If a menu has more than one screen, the Liebert iCOM display will have text at the top simi- lar to this: (page 1 of 2).

5.Press Enter to select the first line of data.

6.Use the Up and Down arrow keys to scroll to the desired data point.

7.Press ESC to move back to higher level menus.

4.1.3Entering the Password

Most settings in the Liebert iCOM are protected by a factory-set password, 1490. To enter the pass- word:

1.From the home screen, press the Enter key to view the User Menu (see Figure 8).

2.Press Enter again to highlight the first icon.

3.Use the keyboard’s arrow keys to move to the icon for the data you wish to change.

4.Once that icon is highlighted, press Enter again to open that menu.

5.Press Enter to highlight the Password line.

6.With the Password line highlighted, press Enter to highlight the first digit in the password

7.Enter the password, 1490.

Use the Up and Down arrow keys to select a numeral for the first digit of the password. Move to the next digit of the password with the Right arrow key.

Select the numerals for all four digits with the same process.

8.After all four digits of the password have been entered, press the Enter key.

NOTE

Do not press the ESC key or the Liebert iCOM will move to the previous screen and the password must be re-entered before changes may be made.

Figure 6 Entering the password

 

After highlighting the Password command line, press

Password command line—highlight

Enter again to highlight the first digit. Use the Up and

by pressing Enter

Down arrow keys to change the first digit. Move to the

 

next digit in the Password with the right arrow.

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT 01

 

 

 

 

 

 

 

 

 

 

U101

PASSWORD

(Actual Level

3)

 

 

 

 

 

 

U102

Temperature Setpoint

 

72°F

 

 

 

U103

Humidity Setpoint

 

50.0%

 

 

 

U104

Humidity Control Type

 

Relative

 

 

 

U105

Supply Sensor

 

 

Disabled

 

 

 

U106

Supply Setpoint

 

 

°F

 

 

 

U107

Backup Temperature Setpoint

73°F

 

 

 

U108

 

 

 

 

 

 

 

U109

 

 

 

 

 

 

 

U110

 

 

 

 

 

 

 

U111

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for nex t /prev uni t

to s el ec t parameter

 

 

 

then

to change parameter

to confirm

 

 

 

 

 

 

 

 

 

 

Password is factory-set at 1490

11