Emerson 3000/ITR manual 6.1Standard Alarms, 6.0ALARM DESCRIPTIONS, 6.1.1Change Filter

Models: 3000/ITR

1 72
Download 72 pages 16.82 Kb
Page 38
Image 38
6.0ALARM DESCRIPTIONS

Alarm Descriptions

6.0ALARM DESCRIPTIONS

The Liebert iCOM will audibly and visually annunciate all enabled alarms. Alarms are wired from Terminal 24 through a normally open contact to locations 50, 51, 55 and 56, respectively, for alarms 1 through 4.

The alarms can be delayed from 0 to 255 seconds.

The alarms can be designated as WARNING, URGENT, or DISABLED. Alarms designated as WARNINGS are annunciated after the Time Delay, but do not energize the Common Alarm Relay. If designated as URGENT, they are annunciated after the Time Delay as a WARNING alarm and then re-annunciated after a user programmable period from 0 minutes to 999 hours as an URGENT alarm. When annunciated as an URGENT alarm, the Common Alarm Relay is activated.

When a new alarm occurs, it is displayed on the screen and the audible alarm is activated. If the Lie- bert Challenger 3000/Liebert Challenger ITR with iCOM is communicating with a Liebert site moni- toring product, the alarm is also transmitted. The display will also show a message to “PRESS ENTER KEY TO SILENCE” the alarm. After the alarm is silenced, the display will return to the Nor- mal Status Display.

The alarms can also be silenced through communications with a Liebert site monitoring unit. Most alarms will reset automatically when the alarm condition is no longer present and only after it has been acknowledged by being “Silenced.” The exceptions are:

The three software alarms: Loss of Power, Low Suction Pressure, and Short Cycle, which reset automatically 90 minutes after being “Silenced” or acknowledged.

Some alarms, such as overloads and high pressure switches, may require a manual reset depend- ing on your model.

An alarms history is retained in nonvolatile memory.

6.1Standard Alarms

6.1.1Change Filter

Periodically, the return air filters in the environmental units must be changed. The Change Filter alarm notifies the user that filter replacement is necessary. A differential air pressure switch closes when the pressure drop across the filters becomes excessive. The switch is adjustable using the proce- dure on the switch label.

6.1.2Compressor Overload

An optional tri-block overload device can be used for the compressor. Compressor overload may be manual or automatic reset, depending on your model. Overload is located at the electric connection box on the compressor.

32

Page 38
Image 38
Emerson 3000/ITR manual 6.1Standard Alarms, 6.0ALARM DESCRIPTIONS, 6.1.1Change Filter, 6.1.2Compressor Overload