The optional Advanced control processor shall be microprocessor based with a front monitor dot matrix display panel and control keys for user inputs. The controls shall be menu driven with
Control
The control system shall allow programming of the following room conditions:
Temperature Setpoint 65 to 85°F
Temperature Sensitivity +1 to +9.9°F (0.6 to 5.6°C) in 0.1° increments
Humidity Setpoint 20 to 80% RH Humidity Sensitivity +1 to +30% RH
All setpoints shall be adjustable from the individual unit front monitor panel.
Temperature and Humidity Sensors shall be capable of being calibrated using the front monitor panel con- trols to coordinate with other temperature and humidity sensors in the room.
Predictive Humidity Control
The microprocessor shall calculate the moisture con- tent in the room and prevent unnecessary humidifi- cation and dehumidification cycles by responding to changes in dew point temperature.
Compressor
The control system shall include a program to pre- vent compressor
System
For
Sequential Load Activation
During
Chilled Water/Hot
Chilled water, hot water, and
Front Monitor Display Panel
The microprocessor shall provide a front monitor 240 x 120 dot matrix display panel with adjustable back- lighting. This display (along with five front mounted control keys) shall be the only operator interface required to obtain all available system information such as room conditions, operational status, graphi- cal data, alarms, control and alarm setpoints, and all user selections including alarm delays, sensor cali- bration, DIP switch selections, and diagnostics. All indicators shall be in language form. No symbols or codes shall be acceptable.
Alarms
The microprocessor shall activate an audible and visual alarm in event of any of the following condi- tions:
High Temperature
Low Temperature High Humidity Low Humidity Short Cycle
Compressor Overload (Optional)
Main Fan Overload (Optional) Humidifier Problem
High Head Pressure Change Filter Loss of Air Flow Low Suction Pressure Loss of Power Custom Alarm (#1 to #4)
Custom alarms are four customer accessible alarm inputs to be indicated on the front panel. Custom alarms can be identified with prepared (pro- grammed) alarm labels for the following frequently used inputs:
Water Under Floor Smoke Detected Standby GC Pump On Loss of Water Flow Standby Unit On
Audible Alarm
The audible alarm shall annunciate any alarm that is enabled by the operator.