The cooling coil shall have a minimum of _____ sq. ft.

(sq. m) face area, _____ rows deep. The coil shall be

controlled by a modulating control valve. The chilled water coil shall be designed for closed-loop applica- tions using properly maintained water. It shall be configured as an (A) (V) frame and be constructed of copper tubes and aluminum fins and have a maxi- mum face velocity of _____ ft. per minute (m/s) at

_____ CFM (CMH). The water circuit shall be

designed to distribute water into the entire coil face area. The coil shall be supplied with _____ °F (°C)

entering water temperature, with a _____ °F (°C)

temperature rise. The coil shall be supplied with

_____ GPM (m/s) of chilled water and the pressure

drop shall not exceed _____ PSI (kPa). The coil

assembly shall be mounted in a stainless steel con- densate drain pan.

3-Way Chilled Water Valve (Standard)

The water circuit shall include a 3-way modulating valve. The microprocessor control shall position the valve in response to room conditions. Cooling capac- ity will be controlled by bypassing chilled water around the coil.

2-Way Chilled Water Valve (Optional)

The water circuit shall include a 2-way modulating valve. The microprocessor control shall position the valve in response to room conditions. The minimum close-off pressure of the valve/actuator assembly shall be _____ PSI (kPa).

Design Pressure

The chilled water circuit shall be designed for a pres- sure of [(150 PSI (1034 kPa)) (400 PSI (2758 kPa))].

Flow Switch (Optional)

The flow switch shall activate the alarm system should the chilled water supply be interrupted. The switch shall be factory mounted and wired.

  

(For detailed Guide Specifications on these products, refer to information posted at www.liebert.com)

SiteScan Web System

SiteLink Module

OpenComms Nform

OpenComms NIC & Web Card (OC-NIC &

OC-Web Card)

Environmental Discrete Outputs Card

(ENV-DO)

Remote Contact Monitor

RCM4

Autochangeover Controllers

AC3

RAC2-8

Universal Monitor

Leak Detection

Direct Read Module

Zone Sensor

Spot Sensor

 

  

 

Install environmental control units in accordance with manufacturer’s installation instructions. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer’s recom- mended clearances.

 

Install and connect electrical devices furnished by manufacturer but not specified to be factory mounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical contractor.

 

Install and connect devices furnished by manufac- turer but not specified to be factory mounted. Fur- nish copy of manufacturer’s piping connection diagram submittal to piping contractor.

 

Connect water supply and drains to air conditioning unit. Provide pitch and trap as manufacturer’s instructions and local codes require.

 

Start up environmental control units in accordance with manufacturer’s start up instructions. Test con- trols and demonstrate compliance with requirements.

