Emerson 3000 manual , , Product

Models: 3000

1 60
Download 60 pages 24.1 Kb
Page 54
Image 54


Piggyback Condenser (Optional)

The system shall be supplied with a piggyback con- denser (PB). The condenser shall be constructed of steel with frame coated using the autophoretic® pro- cess, and panels powder coated to protect against corrosion. The coil shall be copper tube with alumi- num fins. The heavy duty fan shall be the centrifugal type, double width, double inlet. The 1750 RPM (1450 RPM @ 50 Hz) fan motor shall be mounted on an adjustable base, and equipped with an adjustable motor pulley. A Liebert Lee-Temp head pressure con- trol system shall be integral with the unit. The sys- tem shall be designed for -30°F (-34.4°C) ambient. The air cooled condenser shall have a _____ Volt,

3 phase, _____ Hz power supply.

Centrifugal Fan Condenser (Optional)

The system shall be supplied with a centrifugal fan condenser (LCC). The condenser shall be constructed of galvanized steel with a copper tube, aluminum fin coil. The heavy duty fan shall be the centrifugal type, double width, double inlet. The 1750 RPM (1450 RPM @ 50 Hz) fan motor shall be mounted on an adjustable base, and equipped with an adjustable motor pulley. A Liebert Lee- Temp head pressure control system shall be field piped to the unit. Elec- trical controls shall be in a rain-tight enclosure.

The system shall be designed for _____ °F (°C) ambi-

ent. The air cooled condenser shall have a _____ Volt,

3 phase, _____ Hz power supply.

  



The water/glycol system shall be equipped with a coax- ial condenser having a total pressure drop of _____ ft.

of water (kPa) and a flow rate of _____ GPM (l/s) with

_____ °F (°C) entering water/glycol temperature.

2-Way Water Regulating Valve with Bypass (Standard)

The condenser circuit shall be pre-piped with a head- pressure actuated 2-way regulating valve with bypass.

3-Way Water Regulating Valve (Optional)

The condenser circuit shall be pre-piped with a head pressure actuated 3-way regulating valve.

Design Pressure

The condenser water/glycol circuit shall be designed for a pressure of [(150 PSI (1034 kPa)) (350 PSI (2413 kPa))].

Crankcase Heater (Optional)

A crankcase heater is provided to prevent the migra- tion of refrigerant to the compressor during off cycles.

Hot Gas Reheat (Optional)

The complete hot gas reheat system shall include a copper tube, aluminum fin coil, three-way solenoid valve, and refrigerant check valve. The capacity of the coil shall be _____ BTU/HR (kW).



Propeller Fan Drycooler (Standard)

The Liebert manufactured drycooler shall be the low profile, slow speed, direct drive propeller fan type. The drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an inte- gral electric control panel. The drycooler shall be designed for _____ °F (°C) ambient.

Centrifugal Fan Drycooler (Optional)

The system shall be supplied with a centrifugal fan drycooler (LCD). The drycooler shall be constructed of galvanized steel with a copper tube, aluminum fin coil. The heavy duty fan shall be the centrifugal type, dou- ble width, double inlet. The 1750 RPM (1450 RPM @ 50 Hz) fan motor shall be mounted on an adjustable base, and equipped with an adjustable motor pulley. A 3-way control valve and thermostat shall maintain the desired fluid temperature. Electrical controls shall be in a rain-tight enclosure. The system shall be designed for _____ °F (°C) ambient. The drycooler shall have a

_____ Volt, 3 phase, _____ Hz power supply.

Single Glycol Pump Package (Standard)

This system shall be provided with a centrifugal pump mounted in a weatherproof and vented enclo- sure. The pump shall be rated for _____ GPM (l/s) at

_____ ft. of head (kPa), and operate on _____ Volt,

3 phase, _____ Hz.

Dual Glycol Pump Package (Optional)

The dual pump package shall include pumps, enclo- sure, and field mounted flow switch. The pumps shall be wired to the drycooler control box which includes a lead/lag switch for the pumps. The standby pump shall automatically start upon failure of the lead pump. Each pump shall be rated _____ for

GPM (l/s) at _____ feet of head (kPa).

  GLYCOOL Coil

The GLYCOOL coil shall be constructed of copper tubes and aluminum fins and be located upstream of the evaporator coil. The GLYCOOL coil shall be designed for closed-loop applications using properly treated glycol solutions. The coil shall be rated at

_____ BTU/HR (kW) sensible cooling capacity with a

45°F (7.2°C) entering glycol solution temperature. The GLYCOOL coil shall require _____ GPM (l/s) and

the total unit pressure drop shall not exceed _____

feet of water (kPa) when in the free cooling mode.



DISCONTINUED

 

PRODUCT

Page 54
Image 54
Emerson 3000 manual , , Product