3-Way GLYCOOL Valve

The GLYCOOL coil shall be equipped with a fully proportional 3-way control valve. This motorized con- trol valve shall control the amount of flow to the GLYCOOL coil and maintain constant temperature and relative humidity.

Glycol Condenser

The glycol system shall be equipped with a coaxial condenser having a total pressure drop of _____ feet

of water (kPa) and a flow rate of _____ GPM (l/s),

with _____ °F (°C) entering 40% ethylene glycol tem-

perature.

3-Way Water Regulating Valve

The condenser circuit shall be pre-piped with a head pressure actuated 3-way water regulating valve.

Design Pressure

The GLYCOOL coil/condenser circuit shall be designed for a pressure of [(150 PSI (1034 kPa)) (300 PSI (2069 kPa))].

Comparator Circuit

The system shall be equipped with a microprocessor- controlled comparator sensor that permits free-cool- ing operation whenever entering glycol temperature is below return-air temperature.

Propeller Fan Drycooler (Standard)

The Liebert manufactured drycooler shall be the low profile, slow speed, direct drive propeller fan type. The drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an inte- gral electric control panel. The drycooler shall be designed for _____ °F (°C) ambient.

Centrifugal Fan Drycooler (Optional)

The system shall be supplied with a centrifugal fan drycooler (LCD). The drycooler shall be constructed of galvanized steel with a copper tube, aluminum fin coil. The heavy duty fan shall be the centrifugal type, dou- ble width, double inlet. The 1750 RPM (1450 RPM @ 50 Hz) fan motor shall be mounted on an adjustable base, and equipped with an adjustable motor pulley. A 3-way control valve and thermostat shall maintain the desired fluid temperature. Electrical controls shall be in a rain tight enclosure. The system shall be designed for _____ °F (°C) ambient. The drycooler shall have a

_____ Volt, 3 phase, _____ Hz power supply.

Single Glycol Pump Package (Standard)

This system shall be provided with a centrifugal pump mounted in a weatherproof and vented enclo- sure. The pump shall be rated for _____ GPM (l/s) at

_____ ft. of head (kPa), and operate on _____ Volt,

3 phase, _____ Hz.

Dual Glycol Pump Package (Optional)

The dual pump package shall include pumps, enclo- sure, and field mounted flow switch. The pumps shall be wired to the drycooler control box which includes a lead/lag switch for the pumps. The standby pump shall automatically start upon failure of the lead pump. Each pump shall be rated for _____ GPM (l/s)

at _____ feet of head (kPa).

 

Direct Expansion Coil

The evaporator coil shall have _____ sq.ft. (sq. m)

face area, _____ rows deep. It shall be configured as

(A)(V) frame and be constructed of copper tubes and aluminum fins and have a maximum face velocity of

_____ ft. per minute (m/s) at _____ CFM (CMH). The coil shall be provided with a stainless steel drain pan.

Refrigeration System

The refrigeration system shall consist of a rugged scroll compressor, pressure safety switches, exter- nally equalized expansion valve, filter dryer, and a refrigerant sight glass and moisture indicator.

Refrigerant Line Sets (Optional)

Pre-charged refrigerant line sets shall be provided by Liebert in proper lengths for application. Line set length shall be _____ feet (m).



The condenser coil shall be constructed of copper tubes and aluminum fins. The condensing unit shall be factory assembled, charged with refrigerant and sealed.

Components shall include scroll compressor, high- pressure switch, Lee-temp refrigerant receiver, head pressure control valve, and liquid line solenoid valve.

The condensing unit shall be designed for 95°F (35°C) ambient and be capable of operation to -20°F (-29°C) ambient.

A hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low load conditions.

The condenser fan shall be designed for

_____ CFM (CMH) at _____ inches (mm) external

static pressure.

(Optional) Disconnect

Factory installed non-fused disconnect switch allows unit to be turned off for maintenance.

3-Ton Models

The condensing module shall be capable of being con- nected to the evaporator section using pre-charged refrigerant line sets. No brazing, dehydration, or charging shall be required. The fan/motor assembly shall be direct drive.

