Two levels of microprocessor control systems are available providing precise control and monitoring of the critical space.

The Advanced Microprocessor is standard, and the Advanced Microprocessor with Graphics is optional. The main control functions are similar for both controls.



The user must enter a three-digit password before making changes.

Temperature Setpoint 65-85°F (18-29°C)*

Temperature Sensitivity +1-10°F (0.6-5.6°C)

Humidity Setpoint 20-80% RH*

Humidity Sensitivity 1-30% RH

High Temperature Alarm 35-90°F (2-32°C)

Low Temperature Alarm 35-90°F (2-32°C)

High Humidity Alarm 15-85% RH

Low Humidity Alarm 15-85% RH

*The microprocessor may be set within these ranges; however, the unit may not be able to control to extreme combinations of temperature and humidity.



Input diagnostics: Reviews inputs to the con- trol system.

Control board diagnostics: Initiates a self-test of the control system.

Output diagnostics: Tests major components by turning them on and off from the control panel. Includes: main fan, compressor, liquid line solenoid valve, hot gas bypass valve, chilled water or chilled GLYCOOL valve, R-5 relay, reheat, hot water reheat valve, humidifier, humidifier make-up valve, and common alarm.



Alarm history log: The Advanced Microproces- sor displays the 10 most recent alarms. The Advanced Microprocessor with Graphics displays the most recent 60 alarms. Both provide a time and date stamp for each event

Run time log: Displays run time and hours for major components (also allows reset of run hours) including compressors, GLYCOOL, fan, humidifier, and reheat.



Factory set-up for Intelligent Control which uses “fuzzy logic” and “expert systems” methods. Propor- tional and Tunable PID are user selectable options.



Compressor short cycle control: Prevents compressor short-cycling and needless compres- sor wear.

System auto restart: The auto restart feature will automatically restart the system after a power failure. Time delay is programmable.

Sequential Load Activation: On initial start-up or restart after power failure, each operational load is sequenced to minimize total inrush current.

Hot Water / Econ-O-Coil Flush Cycles: Hot water reheat coils and Econ-O-Coils are periodi- cally flushed to prevent a build-up of contami- nants.

Temperature/Humidity Sensor Calibration: The sensors may be calibrated from the front mon- itor panel to insure that all units in the room are similarly calibrated, assuring greater precision.



Normal display: Includes present room temper- ature and humidity, active functions (cooling, heating, dehumidifying), and any alarms.

Operating status: Displays each control opera- tion in percent.

Read analog inputs function: Displays the present values of up to four analog inputs.



Humidifier problem

High head pressure

Change filter

Loss of air flow

High temperature

Low temperature

High humidity

Low humidity

Compressor overload (opt)

Main fan overload (opt)

Low suction pressure

Short cycle

Loss of power

Custom alarm (choose up to 4)

Water under floor

Smoke detected

Standby GC pump on

Loss of water flow

Standby unit on

User customized text

DISCONTINUED

 