Head pressure operated regulating valves accurately control the condensing temperature and maintain system capacity for various entering liquid flow rates and temperatures.
The high pressure option for the condenser circuit consists of a regulating valve and a condenser rated at 350 psig (2413 kPa)
A compressor crankcase heater is available to pre- vent the migration of refrigerant to the compressor during off cycles.
The hot gas reheat assembly consists of a
Factory charged and sealed, the water cooled con- densing unit is ready to be installed quickly and eas- ily. The
Condensing unit has a hot gas bypass standard fea- ture that bypasses hot gas around the compressor directly to the suction side of the compressor to pro- vide capacity control and reduce compressor cycling. System includes liquid injection valve to maintain proper suction superheat.
The high pressure option for the condenser circuit consists of a
Allows unit to be turned off for maintenance. Discon- nect switch is available on indoor condensing units only.
Consists of one
Available in 15 ft. (4.6m) and 30 ft. (9.1m) lengths for interconnection of remote located condenser module. Maximum recommended distance between evapora- tor and condenser with
(3 ton only) - contains two suction and two liquid line compatible fittings that allow
The Liebert manufactured Fan Speed Control dry- cooler is constructed of aluminum and features cop- per tubes and aluminum fin design. It is low profile, propeller fan type and provides quiet, trouble free heat rejection. The drycooler features a variable speed fan motor and a specially engineered solid state fan speed transducer. The transducer senses the temperature of the leaving glycol and modulates the speed of the fan to maintain proper glycol tem- peratures. An integral,
The glycol system includes a matching centrifugal glycol pump. It is mounted in a vented, weatherproof enclosure.
Optional