This document contains information proprietary to Rosemount Analytical, and is not to be made available

to those who may compete with Rosemount Analytical.

11.NO REVISION TO DRAWING WITHOUT PRIOR FACTORY MUTUAL RESEARCH APPROVAL.

10.THE CONFIGURATION OF ASSOCIATED APPARATUS MUST BE FACTORY MUTUAL RESEARCH APPROVED UNDER THE ASSOCIATED CONCEPT.

9.CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 Vrms OR Vdc.

D 1400287

C

B

8.ASSOCIATED APPARATUS MANUFACTURER'S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.

7.THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS

WITH ASSOCIATED APPARATUS WHEN THE FOLLOWING IS TRUE:

FIELD DEVICE INPUT

ASSOCIATED APPARATUS OUTPUT

Vmax OR Ui

Voc, Vt OR Uo;

Imax OR Ii

Isc, It OR Io;

Pmax OR Pi

Po;

3Ci+ 3Ccable;

Ca, Ct OR Co

3Li+ 3Lcable.

La, Lt OR Lo; OR Lc/Rc (La/Ra OR Lo/Ro) AND Li/Ri (La/Ra OR Lo/Ro)

6.RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN 1.0 Ohm.

5.DUST-TIGHT CONDUIT SEAL MUST BE USED WHEN INSTALLED IN CLASS II AND CLASS III ENVIRONMENTS.

 

TABLE I

 

TABLE II

GAS

OUTPUT PARAMETERS

OUTPUT

MODEL 5081-P-FI

GROUPS

Ca

La

PARAMETERS

TB1-1 THRU 12

 

(uF)

(mH)

 

 

 

A, B

0.96

3.1

Vt

13.02 Vdc

C

5.99

12.3

It

105.64 mA

D

21.69

25

Pt

147 mW

TABLE III

5081-P-FI FISCO PARAMETERS

SUPPLY / SIGNAL TERMINALS TB 1-15, 16

B

4. SENSORS WITHOUT PREAMPS SHALL MEET THE REQUIREMENTS OF SIMPLE APPARATUS AS

MODEL NO.

GROUPS

Vmax (Vdc)

Imax (mA)

Pmax (W)

Ci (nF)

Li (uH)

DEFINED IN ANSI/ISA RP12.6 AND THE NEC, ANSI/NFPA 70.

 

IIB/

 

 

 

 

 

THEY CAN NOT GENERATE NOR STORE MORE THAN 1.5V, 0.1A OR A PASSIVE COMPONENT

5081-P-FI

17.5

380

5.32

5

10

THAT DOES NOT DISSIPATE MORE THAN 1.3W. SEE TABLES I AND II.

 

C,D,E,F,G

 

 

 

 

 

 

 

 

 

 

 

 

A

3.INSTALLATION SHOULD BE IN ACCORDANCE WITH ANSI/ISA RP12.06 "INSTALLATION OF INTRINSICALLY SAFE SYSTEMS FOR HAZARDOUS (CLASSIFIED) LOCATIONS" (EXCEPT CHAPTER 5 FOR FISCO INSTALLATIONS) AND THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70) SECTIONS 504 AND 505.

2.PREAMPLIFIER TYPE 23546-00, 23538-00 OR 23561-00 MAY BE UTILIZED INSTEAD OF THE MODEL 5081-P-FI TRANSMITTER INTEGRAL PREAMPLIFIER CIRCUIRTY. A WEATHER RESISTANT ENCLOSURE MUST HOUSE THE TYPE 23546-00 REMOTE PREAMPLIFIER.

1.THE MODEL 5081-P-FI TRANSMITTER INCLUDES INTEGRAL PREAMPLIFIER CIRCUITRY. AN EXTERNAL PREAMPLIFIER MAY BE ALSO USED.

THE OUTPUT PARAMETERS SPECIFIED IN TABLE II ARE VALID FOR EITHER PREAMPLIFIER.

THE CAPACITANCE AND INDUCTANCE OF THE LOAD CONNECTED TO THE SENSOR TERMINALS MUST NOT EXCEED THE VALUES SPECIFIED IN TABLE I

WHERE Ca

Ci (SENSOR) + Ccable;

La

Li (SENSOR) + Lcable.

5081-P-FI

IIC/

17.5

360

2.52

5

10

 

A,B,C,D,E,F,G

 

 

 

 

 

A

 

D

DWG NO.

1400287

 

REV

 

 

 

B

NOTES: UNLESS OTHERWISE SPECIFIED

SIZE

 

 

 

SCALE: NONE

 

TYPE

SHEET 2 OF 2

 

 

 

 

 

08-94

8