TESTING & SERVICE (continued)

TESTING & SERVICE (continued)

TROUBLE-SHOOTING

Note any optional accessories that may be furnished on the ATB and review their operation. Refer to any sepa- rate drawings and/or instructions that may be packed with the ATB.

Hazardous voltage capable of causing shock,

burns, or death is used in this switch. Do not touch the power or load terminals of the transfer switch!

Table 2-1. Trouble-Shooting Checks.

 

CHECK IN NUMERICAL SEQUENCE

PROBLEM

 

 

 

1

2

3

 

OPERATION

GEN-SET

VOLTAGE

Engine–generator set does

Hold Transfer Test switch 15

Starting control must be in the

 

not start when the Transfer

seconds or the outage must

automatic position. Batteries

 

Control switch is turned and

be long enough to allow for

must be charged and

---

held in Transfer Test position

Feature 1C time delay plus

connected. Check wiring to

 

or when normal source fails.

engine cranking and starting.

engine starting contacts.

 

 

 

 

 

Transfer switch does not

Wait for Feature 2B time delay

Generator output circuit

Voltmeter should read at

transfer the load to the

to time out.

breaker must be closed.

least 90% of nominal phase to

emergency source after the

 

Generator frequency must be

phase voltage between

engine–generator set starts.

 

at least 95% of nominal (57

transfer switch terminals EA &

 

 

Hz for a 60 Hz system.) *

EC (or EL1 & EL2 for 2 pole)*

 

 

 

 

Transfer switch does not

Wait for Feature 3A time delay

 

Voltmeter should read at least

transfer the load to normal

to time out.

 

90% of nominal phase to

source when normal returns

 

---

phase voltage between

or when the Transfer Control

 

transfer switch terminals NB &

 

 

switch is released.

 

 

NC, NC & NA, & NA & NB (or

 

 

 

NL1 & NL2 for 2 pole).

 

 

 

 

Engine–generator-set does

Wait for Feature 2E time delay

Starting control must be in the

 

not stop after load retransfer

to time out.

automatic position.

---

to the normal source.

 

 

 

 

 

 

 

* These are factory settings. Refer to Controller User’s Guide.

If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASI. In the United States, call 1–800–800–2726. In Canada, call 1–888–234–2726. Furnish the Serial No., Bill of Material (BOM) No., and Catalog No. from the transfer switch nameplate.

MANUAL LOAD TRANSFER

This procedure manually transfers load to other source if the Transfer Switch or Control Panel are out of service.

!

 

Close all enclosure doors to prevent personal

 

injury in case of electrical system fault.

 

1. Be sure that the Bypass Handle is in the BYPASS

Figure 2–1. Bypass Handle.

POS (position) (see page 3–1).

2.Be sure that the Isolation Handle is in the TEST or DISCONNECTED position (see page 3–2).

3.Turn the Bypass Handle clockwise to AUTOMATIC POS (position).

4.Then pull–out or push–in the Bypass Handle and turn it back to BYPASS POS (select opposite source):

-Emergency Source - pull out the handle

-Normal Source - push in the handle

2--2