Guide Specifications
The Service Menus Shall be Defined as Follows
Setpoints: Menu shall allow setpoints within the following ranges:
•Temperature Setpoint
•Temperature Sensitivity
•Humidity Setpoint
•Humidity Sensitivity
•High Temperature Alarm
•Low Temperature Alarm
•High Humidity Alarm
•Low Humidity Alarm
*The microprocessor may be set within these ranges, however, the unit may not be able to control to extreme combinations of temperature and humidity.
Standby
Timers/Sleep Mode: Menu shall allow various customer settings for turning on/off unit.
Alarm Setup: Menu shall allow customer settings for alarm notification (audible/local/remote). The following alarms shall be available:
•High Temperature
•Low Temperature
•High Humidity
•Low Humidity
•Main Fan Overload (Optional)
•Humidifier Problem
•Change Filter
•Fan Failure
•Unit Off
Audible Alarm: The audible alarm shall annunciate any alarm that is enabled by the operator.
Common Alarm: A programmable common alarm shall be provided to interface user selected alarms with a remote alarm device.
Remote Monitoring: All alarms shall be communicated to the Liebert monitoring system with the
following information: Date and time of occurrence, unit number and present temperature and humidity.
Sensor Calibration: Menu shall allow unit sensors to be calibrated with external sensors.
Maintenance/Wellness Settings: Menu shall allow reporting of potential component problems before they occur.
Options Setup: Menu shall provide operation settings for the installed components.
System/Network Setup: Menu shall allow
Teamwork Modes of Operation: Saves energy by preventing operation of units in opposite modes multiple units.
Auxiliary Boards: Menu shall allow setup of optional expansion boards.
Diagnostics/Service Mode: The Liebert iCOM control shall be provided with