Emerson manual LIEBERT CW PERFORMANCE DATA-MODELS WITH EC FANS, 50 & 60 HZ

Models: CW

1 28
Download 28 pages 34.73 Kb
Page 8
Image 8
Liebert CW Performance Data—Models with EC Fans, 50 & 60 Hz

Liebert CW Performance Data—Models with EC Fans, 50 & 60 Hz

2.0LIEBERT CW PERFORMANCE DATA—MODELS WITH EC FANS, 50 & 60 HZ

 

CW106D

CW114D

 

CW181D

 

 

 

 

 

Capacity Data BTU/Hr (kW) {Based on 45°F (7.2°C) Entering Water. 10°F Water Rise}

 

75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH *

 

 

 

Total -kBTUH (kw)

435 (127.5)

552 (161.7)

 

813 (238.2)

Sensible - kBTUH (kw)

362 (106.1)

423 (123.9)

 

612 (179.3)

Flow Rate-GPM (Vs)

92.1 (5.8)

116.3 (7.4)

 

179.3 (11.4)

Press. Drop- ft (kPa)

27.8 (83.0)

50.2 (149.8)

 

40.0 (119.4)

75°F DB, 61°F WB (23.9°C DB, 16.1 °C WB) 45°% RH *

 

 

 

Total -kBTUH (kw)

395 (115.7)

494 (144.7)

 

725 (212.4)

Sensible - kBTUH (kw)

368 (107.8)

427 (125.1)

 

617 (180.8)

Flow Rate-GPM (Vs)

84.0 (5.8)

104.8 (6.6)

 

153.4 (9.7)

Press. Drop- ft (kPa)

23.5 (70.1)

41.5 (123.8)

 

29.3 (87.4)

72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50% RH *

 

 

 

Total -kBTUH (kw)

341 (99.9)

435 (127.5)

 

642 (188.0)

Sensible - kBTUH (kw)

316 (92.6)

371 (108.7)

 

537 (157.3)

Flow Rate-GPM (Vs)

73.4 (4.6)

93.2 (5.9)

 

136.8 (8.7)

Press. Drop- ft (kPa)

18.3 (54.6)

33.4 (99.7)

 

23.3 (69.5)

72°F DB, 58.6°F WB (22.2°C DB, 14.8°C WB) 45% RH *

 

 

 

Total -kBTUH (kw)

323 (94.6)

395 (115.7)

 

586 (171.7)

Sensible - kBTUH (kw)

323 (94.6)

378 (110.8)

 

546 (160.0)

Flow Rate-GPM (Vs)

69.6 (4.4)

85.2 (5.4)

 

125.7 (8.0)

Press. Drop- ft (kPa)

16.6 (49.5)

28.3 (84.4)

 

19.7 (58.7)

Fan Data

 

 

 

 

Air Volume CFM (CMH)

17,600 (29,920)

17,360 (29,512)

 

24,000 (40,800)

Fan Motor hp Max, (kW), ea, qty 3

4.2 (3.4)

4.2 (3.4)

 

5.2 (4.3)

Ext. Static Press. in. of water (Pa)

0.2 (50)

0.2 (50)

 

0.2 (50)

Chilled Water Coil

 

 

 

 

Face Area sq. ft. (m2)

36.3 (3.4)

36.3 (3.4)

 

71.2 (6.6)

No. of Rows

4

6

 

6

Face Velocity FPM (m/s)

471 (2.3)

471 (2.3)

 

337 (1.6)

Valve Cv

46.2

46.2

 

46.2 qty2

Valve Size - inches

2

2

 

2

Electric Reheat - Three (3) Stage, Fin Tube

 

 

 

 

Capacity BTU/HR (kW)

102,390 (30)

102,390 (30)

 

102,390 (30)

Infrared Humidifier

 

 

 

 

Capacity-Lb. Per Hr. (kg/h)

22.1 (10.0)

22.1 (10.0)

 

22.1 (10.0)

kW

9.6

9.6

 

9.6

FILTER SECTION - DISPOSABLE TYPE - Nominal Sizes and Quantities, MERV7 or MERV11 (option)

Nominal Size, in

24"x31"

24"x31"

21-1/2" x 24"

Quantity

5

5

10

CONNECTION SIZES

 

 

 

Chilled Water-O.D. Copper

2-1/8

2-5/8

3-1/8

Infrared Humidifier-O.D. Copper

1/4

1/4

1/4

Condensate Drain-FPT

1-1/4

 

 

Weight-lb (kg)- Installed

1950 (885)

2090 (949)

2800 (1271)

* Unit capacity data is “net,” and is certified to ASHRAE 127-2007 rating standard

4

Page 8
Image 8
Emerson manual LIEBERT CW PERFORMANCE DATA-MODELS WITH EC FANS, 50 & 60 HZ