Emerson CW manual High Pressure Chilled Water Control Valve-Optional, A-Frame Chilled Water Coil

Models: CW

1 28
Download 28 pages 34.73 Kb
Page 25
Image 25
2.7High Pressure Chilled Water Control Valve—Optional

Guide Specifications

2.7High Pressure Chilled Water Control Valve—Optional

The chilled water circuit shall include a 3-way (2-way) high pressure modulating valve. The valve shall be designed for up to 400 PSI (2758 kPa) water pressure.

2.8A-Frame Chilled Water Coil

The cooling coil shall be of A-frame design with a minimum of ____ sq. ft. (sq.m.) face area, ____ rows

deep.

The coil shall be controlled by a 3-way modulating control valve. It shall be constructed of copper tubes and aluminum fins and have a maximum face velocity of ____ ft. per minute (m/s) at ____ CFM

(CMH).

The water circuit shall be designed to distribute water into the entire coil face area. The coil shall be supplied with ____ °F (°C) entering water temperature, with a ____ °F (°C) temperature rise. The coil

shall require ____ GPM (l/s) of chilled water and the pressure drop shall not exceed ____ PSI (kPa).

The entire coil assembly shall be mounted in a stainless steel condensate drain pan.

For models CW106 and CW114, the end sheets shall be aluminum, and the coil can be removed from the front or either side of the unit.

2.9Flow Switch—Optional

The flow switch shall activate the alarm system should the chilled water supply be interrupted. The switch shall be factory mounted and wired.

2.10Variable Speed Drive—Optional

A variable speed drive (VSD) is available for models CW106 and CW114 to reduce energy consump- tion. The fan motor speed shall be varied from 100% to 60% of rated speed in response to room condi- tions. This shall be controlled automatically by the Liebert iCOM control. The variable speed drive option shall be available with an infrared humidifier.

2.11Optional Components

The computer room environmental control system shall be equipped with the following optional com- ponents.

2.11.1Disconnect Switch—Non-Locking Type

The manual disconnect switch shall be mounted in the high voltage section of the electrical panel. The switch shall be accessible with the door closed.

2.11.2Disconnect Switch—Locking Type

The manual disconnect switch shall be mounted in the high voltage section of the electrical panel. The switch shall be accessible from the outside of the unit with the door closed, and prevent access to the high voltage electrical components until switched to the “OFF” position.

2.11.3High Temp Stat

The high temp stat shall immediately shut down the environmental control system when activated. The high temp stat shall be mounted in the electrical panel with the sensing element in the return air.

2.11.4Condensate Pump, Dual Float

The condensate pump shall have a minimum capacity of 100 GPH at 20 ft. (378 l/hr at 6m) head. (Consult factory for 200V or 230V, 50 Hz applications.) It shall be complete with integral float switch, pump and motor assembly, and reservoir. Secondary float shall shut down unit if tripped.

2.11.5Liebert Liqui-tectSensors (Max. of Two Per Unit)

Provide ____ (quantity) solid state water sensors under the raised floor.

21

Page 25
Image 25
Emerson CW manual High Pressure Chilled Water Control Valve-Optional, A-Frame Chilled Water Coil, Flow Switch-Optional