Emerson 3.1 CW106 and CW114 Electrical Data with EC Fans, Electrical Data-Units With Ec Fans

Models: CW

1 28
Download 28 pages 34.73 Kb
Page 9
Image 9
Electrical Data—Units with EC Fans

Electrical Data—Units with EC Fans

3.0ELECTRICAL DATA—UNITS WITH EC FANS

3.1CW106 and CW114 Electrical Data with EC Fans

Table 1

Electrical data—60Hz-3 phase

 

 

 

 

 

 

 

 

 

 

Reheat

 

Humidifier

Volts

FLA

WSA

OPD

 

 

 

 

 

 

 

Electric

 

Infrared

460

65.4

81.8

90

 

 

 

 

 

 

 

Electric

 

Infrared

575

53.4

66.8

70

 

 

 

 

 

 

 

Electric

 

Infrared

460

53.8

67.3

70

 

 

 

 

 

 

 

Electric

 

Infrared

575

41.8

52.3

60

 

 

 

 

 

 

 

None

 

Infrared

460

26.3

32.9

35

 

 

 

 

 

 

 

None

 

Infrared

575

23.3

29.1

30

 

 

 

 

 

 

 

None

 

None

460

14.7

15.9

20

 

 

 

 

 

 

 

None

 

None

575

11.7

12.7

15

 

 

 

 

 

 

 

Table 2

Electrical data—50Hz-3 phase

 

 

 

 

 

 

 

 

Reheat

 

Humidifier

Volts

FLA

WSA

 

 

 

 

 

 

Electric

 

Electric

400

70.8

88.5

 

 

 

 

 

 

Electric

 

None

400

58

72.5

 

 

 

 

 

 

None

 

Electric

400

27.5

34.4

 

 

 

 

 

 

None

 

None

400

14.7

15.9

 

 

 

 

 

 

3.2CW181 Electrical Data with EC Fans

Table 3

CW181 electrical data—60Hz-3 phase

 

 

 

 

 

 

 

 

 

 

 

Reheat

 

Humidifier

Volts

 

FLA

WSA

OPD

 

 

 

 

 

 

 

 

Electric

 

Infrared

460

 

69

86.3

90

 

 

 

 

 

 

 

 

Electric

 

Infrared

575

 

56.4

70.5

80

 

 

 

 

 

 

 

 

Electric

 

None

460

 

57.4

71.8

80

 

 

 

 

 

 

 

 

Electric

 

None

575

 

44.8

56

60

 

 

 

 

 

 

 

 

None

 

Infrared

460

 

29.9

37.4

35

 

 

 

 

 

 

 

 

None

 

Infrared

575

 

26.3

32.9

35

 

 

 

 

 

 

 

 

None

 

None

460

 

18.3

19.8

25

 

 

 

 

 

 

 

 

None

 

None

575

 

14.7

15.9

20

 

 

 

 

 

 

 

 

Table 4

CW181 electrical data—50Hz-3 phase

 

 

 

 

 

 

 

 

 

Reheat

 

Humidifier

Volts

 

FLA

WSA

 

 

 

 

 

 

 

Electric

 

Electric

400

 

74.4

93

 

 

 

 

 

 

 

Electric

 

None

400

 

61.6

77

 

 

 

 

 

 

 

None

 

Electric

400

 

31.1

38.9

 

 

 

 

 

 

 

None

 

None

400

 

18.3

19.8

 

 

 

 

 

 

 

5

Page 9
Image 9
Emerson manual 3.1 CW106 and CW114 Electrical Data with EC Fans, 3.2 CW181 Electrical Data with EC Fans