Guide Specifications
GUIDE SPECIFICATIONS
1.0GENERAL
1.1Summary
These specifications describe requirements for a precision environmental control system. The system shall be designed to maintain temperature conditions in the rooms containing electronic equipment.
The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements of the room.
1.2Design Requirements
The precision environmental control system shall be a Liebert
HR, (kW) with a sensible cooling capacity of ____ BTU/ HR (kW) based on an entering air temperature
of ____ °F (°C) dry bulb and ____ °F (°C) wet bulb. The unit is to be supplied with ____ volt ____ ph
____ Hz electrical service.
1.3Submittals
Submittals shall be provided with the proposal and shall include:
2.0PRODUCT
2.1Cabinet and Frame Construction
The frame shall be constructed of heliarc welded tubular steel. It shall be painted using the auto- phoretic coating process for maximum corrosion protection. The exterior panels shall be insulated with a minimum 1 in. (25.4mm), 1.5 lb. (0.68 kg) density fiber insulation. The main front panel shall have captive 1/4 turn fasteners. The main unit color shall be _________. The accent color shall be
_________. The exterior panels shall be powder coated.
2.2Filter Chamber
The filter chambers shall be an integral part of the system, located within the cabinet serviceable from either end of the unit. The filters shall be rated not less than ____% efficiency (based on
ASHRAE 52.1).
For models CW106 and CW114, the filters shall be serviceable from the front of the unit.
2.3Fan Section
The fan shall be the centrifugal type, double width double inlet, and shall be
50 Hz) and mounted on an adjustable slide base. The drive package shall be
2.3Electronically Commutated (EC) Fan
The fan shall be the plug/plenum type, single inlet and shall be dynamically balanced. The fan motor shall be 4.2 hp, 1520 rpm maximum operating speed. The drive package shall be direct drive Electron- ically Commutated, variable speed. The fans shall be located to draw air over the
2.4Liebert iCOM™ Microprocessor Control With Small Graphic Display
The Liebert iCOM unit control shall be