5.3Connect Input/Output Power

Installation and Configuration

1.Visually inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Liebert® representative.

2.For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift up to remove. Optional rack-mount handles are shipped with the external battery cabinet and may be installed at this time if desired.

3.Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.

4.Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base extensions ships with each external battery cabinet.

5.Put the UPS in Bypass Mode by pressing the bypass button on the front of the unit one time.

6.Verify the External Battery Cabinet breaker is in the Off position.

7.Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS.

8.Turn the External Battery Cabinet breaker to the On position.

9.Press the On button on the front of the UPS for 4 seconds to return the unit to inverter Mode.

10.Verify the circuit breaker on the External Battery Cabinet is in the On position.

11.Use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for the configuration program are in 6.0 - Configuration Program.

12.The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 11.

NOTE

When removing the External Battery Cabinet, the circuit breaker on the rear of the cabinet must be turned off before disconnecting the cable.

NOTE

If the UPS is to be shipped or stored for an extended time, the connector should be disconnected. This will minimize any standby current drain on the batteries and help attain their design life.

5.3Connect Input/Output Power

Figure 9 Power Distribution box removal—captive screws and maintenance bypass breaker

 

 

 

 

Maintenance

 

 

 

 

Extract these

 

 

Bypass Breaker

 

 

 

 

captive screws

 

 

The UPS should arrive with the power distribution box attached. If the box needs to be removed for maintenance or replacement, follow these instructions to remove and install the power distribution pack.

To remove:

1.Ensure maintenance bypass lamp is on. To place the unit in maintenance bypass, see 8.4 - Put the Liebert® GXT3in Manual Bypass.

2.Loosen one captive screw over the maintenance bypass breaker.

3.Turn the maintenance bypass breaker on.

NOTICE

The load is unprotected from disturbances in the power supply while the UPS is on bypass.

14