Installation and Configuration

4.Turn the output and input breaker off.

5.Loosen other captive screws until the power distribution box releases.

6.Remove the power distribution box from the UPS and set it aside.

7.Loosen screws over the plastic cover for the connector on the rear of the panel.

8.Slide plastic cover over connector and tighten screws.

NOTE

Do not operate the UPS with this box removed. To disconnect all power to this box and load, the utility input power also must be disconnected.

To install:

1.Align connectors and press box onto UPS

2.Hold box firmly against UPS and tighten captive screws except one over the maintenance bypass breaker.

3.Turn the output and input breaker on.

4.Start the UPS according to startup instructions.

5.Verify that the UPS lamp is illuminated.

6.Turn the maintenance bypass breaker off.

7.Insert the maintenance bypass cover behind the captive screw and tighten the screw.

NOTE

The maintenance bypass breaker cover must be installed behind the captive screw and the screw must be tightened for the UPS to operate in inverter mode.