6.0CONFIGURATION PROGRAM

Configuration Program

6.0CONFIGURATION PROGRAM

The final step of installation may require custom configuration of your UPS using the enclosed configuration program. Some configuration settings may be changed only while the UPS is off. These should be set before the UPS is put into full-time service powering the critical load.

For most users operating with 230VAC and with no external batteries, the factory default settings will be adequate.

6.1Configuration Program Features

Select L-N output voltages to match local voltages.

Enable/Disable Auto-Restart.

Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.

Set the Low Battery Warning alarm time from 2 to 30 minutes.

Enable/Disable the Auto-Battery test.

Set the Auto-Battery test to 7, 14, 21 or 28 days.

Specify the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Liebert® software products.

Modify the shutdown setting of the terminal block (for information on pin assignments, see Table 2).

6.1.1What You Will Need

In addition to the Liebert GXT3UPS, you will need the configuration program CD and USB cable included in the UPS accessory box. A Windows 95® or later computer, desktop or laptop, is also required to set up and run the configuration program.

17