Maintenance
Figure 17 Pulling out the battery packs
Internal
Battery
Pack
Battery |
| |
Handle | Each model has two | |
Pull Out with Battery Handle | ||
battery packs |
6.Unpack a new internal battery pack. Take care not to destroy the packing.
Compare the new and old internal battery packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are different, stop and contact your local Emer- son representative or Emerson Channel Support.
7.Line up and slide in the new internal battery pack.
8.Repeat Steps 6 7 if replacing both battery packs. Each model has two battery packs
9.Reconnect the battery plugs and battery receptacles.
10.Gently push the battery wire into the UPS battery compartment.
11.Reattach the front battery door with the six screws.
12.Reattach the front plastic bezel cover to the UPS.
NOTE
The internal battery pack is
10.2Battery Charging
The batteries are
If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.
10.3Precautions
Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:
•Turn Off and unplug the Liebert GXT3 before cleaning it.
•Wear rubber gloves and boots.
•Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
•Never block or insert any objects into the ventilation holes or other openings of the UPS.
•Do not place the Liebert GXT3 power cord where it might be damaged.
28