User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D) Chapter 3. Local Display Menus 85
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page) Local Menu Flow Diagrams
Settings
AlarmSetting
PowerSystem
Rectifier
Battery
BattFuseUnit
DC
LVD
AC
EIB
SMDU
Converter
SMTemp
Communication
Controller
ESC
B1
B
B3
B2
ENT
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
B5
B4
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ENT
ENT
ENT
ENT
ENT
Language
English
Date
2010-06-30
Time
13:04:10
KeypadVoice
On (on/ off)
ReloadConfig
Yes
DownloadConfig
Yes
AutoConfig
Yes
DHCP
Disabled (enabled/ disabled)
IPAddress
126.50.143.70
SubnetMask
255.255.255.0
DefaultGateway
0.0.0.0
Rectifier
AllRect Set
Rect#1
Rect#2
RectifierID
2 (1-999)
RectPhase
B (A/B/ C)
HVSD
Enabled (enabled/ disabled)
HVSDLimit
59.0V (56.0-59.5)(28.0-29.7)
Restarton HVSD
Enabled (enabled/ disabled)
HVSDRestartT
300s (0-300)
StartInterval
0s (0-10)
Walk-In
Enabled (enabled/ disabled)
Walk-InTime
8s (8-128)
TurnOnACOverV
No (no/yes)
ECOMode
Disabled (enabled/disabled)
BestOper Point
80% (30-90)
FluctRange
10% (1-50)
EnergySave Pt
45% (10-90)
CyclePeriod
168h (1-8760)
RectsON Time
120min (0-255)
TurnOffDelay
5min (1-60)
InputCurr Lmt
30A (1-50)
MixHEPower
Non-Derate (non-derate/ derate)
DGPwr Lmt
Enabled (disabled/ enabled)
DieselDI Input
None (none/ Digital Input 1 / ... / Digital Input8)
DGPwr Lmt Pt
40.0% (40-100)
CurrentLimit
Enabled (enabled/ disabled)
CurrentLimit Pt
400A (dependenton # of rectifiers)
ESC
ENT
ESC
ENT
AC
RectAC
NominalPH-Volt
220V (50-450)
MainsFail Alm1
20% (0.0-100.0)
MainsFail Alm2
20% (0.0-100.0)
ENT
ESC
AllRect Set
AlarmSetting
PowerSystem
Battery
LVD
EIB
Rect#1
Communication
Controller
RectAC
ENT
ENT
ESC
B6
ESC
SMDU
B7
ESC
SMTemp
ESC
ENT
ShuntCurrent
150.0A (50.0-50000.0)
ShuntVoltage
25.0mV (1.0-150.0)
LoadShuntExist
No (No / Yes)
DC
Numof Bat Fuse
0
BattFuseUnit
Converter
AllConv Set
Conv#1
Conv#2
OutputVoltage
52.0V (48.0-55.5)
UnderVoltage
47.0V (42.0-55.0)
OverVoltage
56.0V (49.0-59.0)
OverCurrent
500A (1-500)
HVSD
Enabled (enabled/ disabled)
HVSDLimit
59.0V (48.0-60.0)
CurrentLimit
Enabled (enabled/ disabled)
CurrentLimit Pt
94A (dependenton # of converters)
ESC
ENT
ENT
AllConv Set
SetConv ID
1 (1-999)
ESC
Conv#1
ToSelect a Sub-Menu:
Press or tomove
cursorin menu screen
(selectsmenu item).
PressENT to enter
selectedsub-menu.
ToChangea Parameter:
Press or tomove
upand down list of
parameters.
PressENT to highlight
selectedparameter.
Press or tochange
highlightedvalue.
PressENT to
makethe change.
PressESC to
cancelthe change.
Theparameter values
shownin ( ) are the
adjustmentrange or
acceptablevalues.
Factorydefault settings
arelisted in the ACU+
ConfigurationDrawing (C-dwg)
furnishedwith your system.