User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D) Chapter 3. Local Display Menus 89
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page) Local Menu Flow Diagrams
ESC
B5
ENT EIB
EIB1
Shunt1 Current
500.0A (50.0-50000.0)
Shunt1 Voltage
75.0mV (1.0-150.0)
Shunt2 Current
500.0A (50.0-50000.0)
Shunt2 Voltage
75.0mV (1.0-150.0)
Shunt3 Current
500.0A (50.0-50000.0)
Shunt3 Voltage
75.0mV (1.0-150.0)
NumBatt Shunts
0 (0-3)
NumLoad Shunts
0 (0-3)
VoltageType
48(Block 4) (disable/ 24 (block 2) /
midpoint/ 48 (block 4))
BlkV Diff(12V)
1 (0- 2)
BlkV Diff(Mid)
1 (0- 2)
BlockIn-Use
0 (0-8)
EIB1
ESC
B7
ENT SMTemp
SMTemp1
T1Assign Equip
Ambient (None/Battery / Ambient)
...
T8Assign Equip
None (None/ Battery / Ambient)
SMTemp1
ESC
B6
ENT SMDU
SMDU1
Shunt1 Voltage
75mV (25-75)
Shunt1 Current
500A (100-2000)
Shunt2 Voltage
75mV (25-75)
Shunt2 Current
500A (100-2000)
Shunt3 Voltage
75mV (25-75)
Shunt3 Current
500A (100-2000)
Shunt4 Voltage
75mV (25-75)
Shunt4 Current
500A (100-2000)
Shunt5 Voltage
75mV (25-75)
Shunt5 Current
500A (100-2000)
SMDU1
ESC
B4
ENT
ENT
LVD
LVDGroup
LVDUnit
SMDU1 LVD
HTDRecon Point
38.0deg. C (20-80)
HTDPoint
40.0deg. C (20-80)
LVDGroup
ESC
LVD1
Enable (enable/ disable)
LVD1Mode
Voltage (voltage / time)
LVD1Volt
42.0V (40-60)(20-30)
LVD1ReconVolt
49.0V (40-60)(20-30)
LVD1ReconDelay
1min (1-30)
LVD1Time
300min (30-1000)
LVD1Dependency
None (none / LVD1/ LVD2)
LVD2
Enable (enable/ disable)
LVD2Mode
Voltage (voltage / time)
LVD2Volt
42.0V (40-60)(20-30)
LVD2ReconVolt
49.0V (40-60)(20-30)
LVD2ReconDelay
1min (1-30)
LVD2Time
600min (30-1000)
LVD2Dependency
None (none / LVD1/ LVD2)
HTD1
Disable (enable / disable)
HTD2
Disable (enabled / disable)
LVDType
Bistable (bistable/ mono-stable / mono w/sample)
LVDUnit
LVD1
Enable (enable/ disable)
LVD1Mode
Voltage (voltage / time)
LVD1Voltage
42.0V (40-60)(20-30)
LVD1ReconVolt
49.0V (40-60)(20-30)
LVD1ReconDelay
1min (1-30)
LVD1Time
300min (30-1000)
LVD1Dependency
None (none / LVD1/ LVD2)
LVD2
Enable (enable/ disable)
LVD2Mode
Voltage (voltage / time)
LVD2Voltage
42.0V (40-60)(20-30)
LVD2ReconVolt
49.0V (40-60)(20-30)
LVD2ReconDelay
1min (1-30)
LVD2Time
600min (30-1000)
LVD2Dependency
None (none / LVD1/ LVD2)
HTD1
Disable (enable / disable)
HTD2
Disable (enabled / disable)
SMDU1 LVD
ENT
ESC
ENT
ESC
Displayedwhen Voltage Type
setfor other then disableand
BlockIn-Useset for other then 0.