User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D) Chapter 3. Local Display Menus 87
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page) Local Menu Flow Diagrams
PowerSystem
General
PowerSplit
SlaveCurrLmt
60% (10-90)
DeltaVolt
0.5V (0.1-2.0)
ProportionCoeff
30.0 (0-100)
IntegralTime
60s (10-2000)
ENT
ENT
ESC
ESC
ESC
B2
ENT
PowerSplit
ToChange a Parameter:
Press or tomove up and
downlist of parameters.
PressENT to highlight selected parameter.
Press or tochange highlighted value.
PressENT to make the change.
PressESC to cancel the change.
Theparameter values shown in ( ) are the
adjustmentrange or acceptable values.
Factorydefault settings are listed in the
ACU+Configuration Drawing (C-dwg)
furnishedwith your system.
ToSelect a Sub-Menu:
Press or tomove cursor in
menuscreen (selects menu item).
PressENT to enter selected sub-menu.
Auto/ManState
Auto (auto/ manual)
ManualModeL mt
1h (0-24)
MtncCycle Time
360days (10-7200)
EStop/EShutdown
Disabled (disabled/EStop / EShutdown)
LoadCurrAlarm
3000A (0-4000)
AlarmBlocked
Normal (normal/blocked)
RectExpansion
Inactive (inactive / primary / secondary)
Address(Slave)
201 (201 / 202 / 203)
OverVoltage1
57.0V (40-60) (20-30)
OverVoltage2
58.0V (40-60) (20-30)
UnderVoltage1
48.0V (40-60) (20-30)
UnderVoltage2
44.0V (40-60) (20-30)
FailSafe
enable (disable/ enable)
HybridMode
disable (disable/fixed daily /capacity)
DGRunO vertemp
enable (disable/ enable)
DGRunTime
60min (30-120)
DGUsed
DG1 (DG1/ DG2 / Both)
DIfor Grid
DI3 (DI1 / .../DI 8)
DOD
40.0% (20-80)
DschDuration
12hours (1-22)
StartDsch Time
19clock (0-24)
HighLoad Set
40.0% (20-80)
EqualStartTime
8clock (0-24)
DGAlarmDelay
60sec. (30-180)
FailSafe
NormallyOpen (normallyopen/normally close)
ContactorMode
MasterCtrlr (MasterCtrlr/ SlaveCtrlr)
RelayTest
Disabled (disabled/automatic / individual)
RelayTestTime
45sec. (0-120)
HighLoadLevel1
70% (0-100)
HighLoadLevel2
85% (0-100)
DI1AlarmState
High (Low/ High)
...
DI8AlarmState
High (Low/ High)
AmbTempSensor
IB2T2 (None / SMTemp8T8 / ... / SMTemp8 T1 / ... /
SMTemp1T8/ ... / SMTemp1 T1 / EIBT2 / EIB T1 /
IB2T2/ IB 2T1 / System T3 / System T2 / System T1 /
Average/Ma ximum)
AmbTempHigh2
100.0deg.C (-40to+100)
AmbTempHigh1
90.0deg.C (-40 to +100)
AmbTempLow
-10.0deg.C (-40to+ 100)
SystemTemp1
None (None/Battery/ Ambient)
SystemTemp2
None (None/Battery/ Ambient)
SystemTemp3
None (None/Battery/ Ambient)
IB2Temp1
Battery (None/Battery /Ambient)
IB2Temp2
Ambient (None/ Battery / Ambient)
EIBTemp1
None (None/Battery/ Ambient)
EIBTemp2
None (None/Battery/ Ambient)
Special
Configurations
Only
General
Thetemperature
monitoredby the
Temp.Probeselected
hereis displayedo n
theHomepage of
theWebInterface.