User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D) Chapter 3. Local Display Menus 91
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page) Local Menu Flow Diagrams
QuickSetting
Auto/Manual
ECOMode Set
FLT/EQVolt
FLT/EQSet
TempComp
RectExpansion
E
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ESC ESC
ESC
ESC
ESC
ESC
ESC
Auto/ManState
Auto (auto/ manual)
FloatVoltage
54.0V (42.0-50.0)(21.0-29.0)
EQVoltage
56.5V (42.0-58.0)(21.0-29.0)
RectExpansion
inactive (inactive/ primary / secondary)
Address(Slave)
201 (201 / 202 / 203)
Auto/Manual
ECOMode Set
FLT/EQVolt
FLT/EQSet
TempComp
RectExpansion
ToChange a Parameter:
Press or tomove up and
downlist of parameters.
PressENT to highlight selected parameter.
Press or tochange highlighted value.
PressENT to make the change.
PressESC to cancel the change.
Theparameter values shown in ( ) are the
adjustmentrange or acceptable values.
Factorydefault settings are listed in the
ACU+Configuration Drawing (C-dwg)
furnishedwith your system.
ToSelect a Sub-Menu:
Press or tomove cursor in
menuscreen (selects menu item).
PressENT to enter selected sub-menu.
ECOMode
Enabled (disabled/enabled)
EnergySave Pt
45% (10-90)
BestOper Point
80% (30-90)
FluctRange
10% (1-50)
CyclePeriod
168hour (1-8760)
RectsON Time
120min (0-255)
TurnOff Delay
5min (1-60)
AutoEQ
No (no/ yes)
EQStart Curr
0.060C10 (0.040-0.080)
EQStart Cap
80.0% (0-99)
EQStop Curr
0.010C10 (0.002-0.020)
EQStop Delay
180min (0-1440)
MaximumEQ Time
1080min (60-2880)
CycEQ
No (no/ yes)
CycEQ Interval
100days (2-365)
CycEQ Duration
720min (30-2880)
TempCompCenter
25.0deg. C (0.0-40.0)
TempCompCoeff
72.0mV/deg. C (0.0-500.0)
TempCompSensor
None (None/ SMTemp8 T8 / ... / SMTemp8T1 / ... /
SMTemp1T8/ ... / SMTemp1 T1 / EIB T2 / EIBT1 /
IB2T2 / IB2 T1 / SystemT3 / System T2 / System T1 /
AverageSMBRC / Average / Maximum)
CompTempHigh2
60deg. C (0-100)
CompTempHigh1
50deg. C (0-100)
CompTempLow
-10.0deg. C (-40to+100)
TempCompClamp
Enabled (disabled / enabled)
TempCompMax V
29.0 (42.0-58.0)(21.0-29.0)
TempCompMin V
26.0 (42.0-58.0)(21.0-29.0)
Thetemperature
monitoredby the
Temp.Probeselected
hereas the TempComp
Sensoris also displayed
onthe Homepage of
theWeb Interface as
batterytemperature.