UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D) 88 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page) Local Menu Flow Diagrams
Battery
Basic
Charge
Test
TempComp
Capacity
Battery1
NumBattShun ts
1 (0-2)
CalcBattCurr
No (no/ yes)
LowCapacityPt
75% (25-100)
CurrentLimited
No (no/ yes)
BTRMTempSensor
IB2T2 (None/S MTemp8T8 / ... /SMTemp8T1 / ... /
SMTemp1T8/ ... / SMTemp1 T1 / EIB T2 / EIB T1 /
IB2T2/ IB2 T1 / System T3 / System T2 / System T1 /
AverageSMBRC/ Average / Maximum)
BTRMTempHigh2
100.0deg.C (0-100)
BTRMTempHigh1
90.0deg.C (0-100)
BTRMAction
Disabled (disabled/lo wer voltage)
BTRMVoltage
51.0V (45-55)(22.5-27.5)
ABCLPoint
20A (1-60)
FloatVoltage
54.0V (42.0-58.0)(21.0-29.0)
EQVoltage
56.5V (42.0-58.0)(21.0-29.0)
BattCurrL imit
0.10C10 (0.10-0.25)
OverCurrLm t
0.30C10 (0.30-1.00)
AutoEQ
No (no / yes)
EQStart Curr
0.060C10 (0.040-0.080)
EQStart Cap
80.0% (0-99)
EQStopCu rr
0.010C10 (0.002-0.020)
EQStopDe lay
180min (0-1440)
MaximumEQTime
1080min (60-2880)
CycEQ
No (no/yes)
CycEQ Interval
100days (2-365)
CycEQ Duration
720min (30-2880)
TestVoltLmt
45.0V (43.0-53.5)(21.5-27.0)
TestEndVolt
45.2V (43.2-53.5)(21.5-27.0)
EndTestTime
100min (10-1440)
EndTestCapacity
70% (0-100)
RecordThreshold
0.100V (0.100-1.000)
ACFailTest
Disabled (disabled/e nabled)
PlannedTests
0 (0-12)
Test1(M-D Hr)
10-2110
ConstCurrTest
Disabled (disabled/e nabled)
ConstCurrTCurr
9999.0A (1-9999)
ShortTest
Disabled (disabled/e nabled)
ShortTestCycle
30days (1-365)
ShortTestTime
5min (1-60)
MaxDiffCu rr
0.05C10 (0.00-1.00)
BattTestLowCap
99% (70-100)
TempCompCenter
25.0deg.C (0.0-40.0)
TempCompCoeff
72.0mV/deg.C (0.0-500.0)
TempCompSensor
None (None/ SMTemp8T8/ ... / SMTemp8 T1 / ... /
SMTemp1T8/ ... / SMTemp1T1 / EIB T2 / EIB T1 /
IB2T2/ IB2 T1 / System T3 / System T2 / System T1 /
AverageSMBRC/ Average / Maximum)
CompTempHigh2
60deg. C (0-100)
CompTempHigh1
50deg. C (0-100)
CompTempLow
-10.0deg. C (-40to+100)
TempCompMax V
29.0 (42.0-58.0)(21.0-29.0)
TempCompClamp
Enabled (disabled/ enabled)
TempCompMin V
26.0 (42.0-58.0)(21.0-29.0) ChargingEff
96% (10-100)
Time0.1C10
10.00h (0.00-10.00)
Time0.2C10
4.90h (0.00-10.00)
Time0.3C10
3.00h (0.00-10.00)
Time0.4C10
2.00h (0.00-10.00)
Time0.5C10
1.40h (0.00-10.00)
Time0.6C10
1.20h (0.00-10.00)
Time0.7C10
1.10h (0.00-10.00)
Time0.8C10
0.90h (0.00-10.00)
Time0.9C10
0.70h (0.00-10.00)
Time1.0C10
0.50h (0.00-10.00)
RatedCapacity
600.0Ah (50.0-50000.0)
ShuntCurrent
800.0A (50.0-50000.0)
ShuntVoltage
25.0mv (1.0-150.0)
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ESC
B3
ENT
Basic
Charge
Test
TempComp
Capacity
Battery1
ToChangea P arameter:
Press or tomoveup and
downlist of parameters.
PressENT to highlight selected parameter.
Press or tochangehighlighted value.
PressENT to make the change.
PressESC to cancel the change.
Theparameter values shown in ( )are the
adjustmentrange or acceptable values.
Factorydefault settings are listed in the
ACU+Configuration Drawing (C-dwg)
furnishedwith your system.
ToSelect a Sub-Menu:
Press or tomovecursor in
menuscreen (selects menu item).
PressENT to enter selected sub-menu.