Empire Comfort Systems DVP42FP, P)-2 installation instructions Green LED Status Codes

Models: DVP42FP P)-2

1 72
Download 72 pages 3.7 Kb
Page 57
Image 57
Green LED Status Codes

INTERMITTENT PILOT TROUBLESHOOTING (continued)

Green LED Status Codes

Green LED

 

 

 

Flash Code

 

 

 

(X + Y)a

Indicates

Next System Action

Recommended Service Action

OFF

No “Call for Heat”

Not applicable

None

Flash Fast

Startup-Flame sense calibration

Not applicable

None

Heart Beat

Normal operation

Not applicable

None

3

Recycle

Initiate new trial for ignition. Flash code

If system fails to light on next trial for

 

- Flame failed during run

will remain through the ignition trial

ignition, check gas supply, pilot burner,

 

 

until flame is proved.

flame sense wiring, contamination of

 

 

 

flame rod, burner ground connection.

4

Flame sensed out of sequence

If situation self corrects within 10 sec-

Check for pilot flame. Replace gas valve

 

 

onds, control returns to normal sequence.

if pilot flame present. If no pilot flame,

 

 

If flame out of sequence remains longer

cycle “Call for Heat.” If error repeats,

 

 

than 10 seconds, control goes to Flash

replace control.

 

 

code 6 + 4 (see below).

 

7

Flame sense leakage to ground

Control remains in wait mode. When

Check flame sense lead wire for damage

 

 

the fault corrects, control resumes nor-

or shorting. Check that flame rod is in

 

 

mal operation after a one minute delay.

proper position.

 

 

 

Check flame rod ceramic for cracks,

 

 

 

damage or tracking.

8

Low secondary voltage supply -

Control remains in wait mode. When

Check transformer andAC line for proper

 

below 15.5 Vac)

the fault corrects, control resumes nor-

input voltage to the control. Check with

 

 

mal operation after a one minute delay.

full system load on the transformer.

6 + 2

Failed trial for ignition resulting

Remain in lockout until “Call for Heat”

Check gas supply, pilot burner, spark

 

in lockout

is cycled.

and flame sense wiring, flame rod con-

 

 

 

taminated or out of position, burner

 

 

 

ground connection.

6 + 3

More than 5 flame failures during

Remain in lockout until “Call for Heat”

Check gas supply, pilot burner, flame

 

run on the same “Call for Heat”

is cycled.

sense wiring, contamination of flame

 

resulting in lockout

 

rod, burner ground connection.

6 + 4

Flame sensed out of sequence -

Control waits until flame is no longer

Check for pilot flame. Replace gas valve

 

longer than 10 seconds

sensed and then goes to soft lockout.

if pilot flame present. If no pilot flame,

 

 

Flash code continues. Control auto re-

cycle “Call for Heat.” If error repeats,

 

 

sets from soft lockout after one hour.

replace control.

ON

Soft lockout due to error detected

Control auto resets from soft lockout af-

Reset by cycling “Call for Heat.” If er-

 

during self check sequences

ter one hour.

ror repeats, replace the control.

aFlash Code Descriptions:

-Flash Fast: Rapid blinking

-Heartbeat: Constant 1/2 second bright 1/2 second dim cycles

-A single flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats the sequence.

-X + Y flash codes signify that the LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for three seconds, and then repeats the sequence.

21759-6-0608