GAS SUPPLY

The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Tubing, Type L

 

Inside Diameter

Outside Diameter

 

 

 

 

 

 

Nat.

L.P.

Nat.

L.P.

 

 

 

 

 

0-10ft

1/2"

3/8"

1/2"

3/8"

0-3m

12.7mm

9.5mm

12.7mm

9.5mm

 

 

 

 

 

11-40ft

1/2"

1/2"

5/8"

1/2"

4-12m

12.7mm

12.7mm

15.9mm

12.7mm

 

 

 

 

 

41-100ft

1/2"

1/2"

3/4"

1/2"

13-30m

12.7mm

12.7mm

19mm

12.7mm

 

 

 

 

 

101-150ft

3/4"

1/2"

7/8"

3/4"

31-46m

19mm

12.7mm

22.2mm

1.9 mm

 

 

 

 

 

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

ANS Z21.24Appliance Connectors of Corrugated MetalTubing and Fittings.

ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction.The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.

 

 

Figure 6

 

 

 

 

 

 

Gas Supply Pressure (inches w.c.)

 

 

 

 

 

 

Minimum

Normal

 

Maximum

 

 

 

 

 

Natural Gas

4.5"

7.0"

 

*14.0"

 

 

 

 

 

LP (Propane)

10.8"

11.0"

 

*14.0"

 

 

 

 

 

Manifold Pressure (inches w.c.)

 

 

 

 

 

 

Normal (HI)

 

 

 

 

 

 

Natural Gas

 

3.5"

 

 

 

 

 

 

 

LP (Propane)

 

10.0"

 

 

*NOTE: Remote "RF" Models - 10.5" w.c. maximum

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not ad- equate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

NOTE: The millivolt gas controls are equipped with a captured screw type pressure test point, therefore it is not necessary to provide a 1/8" test point up stream of the control.

Ondirectignitionvalves,hexplugsmaybereplacedwithhosefittings for pressure checks, then reinstalled before operating fireplace.

When using copper or flex connector use only approved fittings.

The appliance and it’s individual shut off valve must be disconnected from supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).

The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa).

Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result in a hazardous condition.

Checking Manifold Pressures

Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 14.0" w.c. (3.484kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet

with the inlet pressure to the valve from a minimum of 10.8" w.c. (2.68kPa) for the purpose of input adjustment to a maximum

of 14.0" w.c. (3.484kPa).

Figure 7

21759-6-0608

Page 9

Page 9
Image 9
Empire Comfort Systems DVP42FP, P)-2 GAS Supply, Installing a New Main Gas Cock, Checking Manifold Pressures

DVP42FP, P)-2 specifications

Empire Comfort Systems has established itself as a leader in the heating and venting industry, providing innovative solutions that cater to modern home heating needs. One of their standout products is the Empire Comfort Systems DVP42FP,P)-2, a direct vent gas fireplace that seamlessly combines aesthetics, efficiency, and technology.

At the heart of the DVP42FP,P)-2 is its contemporary design, which enhances the ambiance of any living space. With a sleek glass front and a range of stylish finishes, this fireplace serves as a perfect centerpiece, embodying both function and fashion. The generous viewing area allows for an unobstructed view of the mesmerizing flames, creating a cozy atmosphere in any room.

This fireplace is engineered for efficiency and performance. With an impressive heating output, the DVP42FP,P)-2 can effectively warm spaces while consuming minimal fuel. It boasts a high-efficiency rating, ensuring that homeowners can enjoy the warmth without incurring high energy costs. The direct vent technology allows for a sealed combustion system that draws air from outside while expelling exhaust gases directly outdoors. This ensures that the air quality inside the home is maintained while providing optimal heating performance.

Ease of use is another hallmark of the DVP42FP,P)-2. It features an intuitive remote control system, allowing users to adjust the temperature and flame settings conveniently from anywhere in the room. This level of user-friendly control enhances the overall experience, making it easy to create the perfect environment.

Another notable characteristic of this model is its safety features. Equipped with safety screens and an auto shut-off feature, the DVP42FP,P)-2 is designed to offer peace of mind, allowing families to enjoy their fireplace without worries about safety.

Maintenance is straightforward with the DVP42FP,P)-2, thanks to its accessible design. Regular upkeep is minimal, allowing homeowners to spend more time enjoying the warmth and beauty of their fireplace rather than worrying about system maintenance.

In conclusion, the Empire Comfort Systems DVP42FP,P)-2 is a captivating, efficient, and technologically advanced direct vent gas fireplace. With its modern design, high efficiency, user-friendly controls, and robust safety features, it represents a wise investment for anyone looking to enhance their home's comfort and aesthetic appeal. Whether for a new build or a renovation, this fireplace stands out as a premier choice for discerning homeowners.