INTERMITTENT PILOT TROUBLESHOOTING

Call Serviceman

GENERAL: All fireplaces have been fire-tested to check for proper operation. This includes, main burner flame, pilot flame, fan opera- tion, fan control, limit control and automatic valve operation. If the fireplace fails to function on initial installation, it is advisable to re-check the following:

1.115 volts to the junction box.

2.Inlet gas pressure.

3.The 24 volt system.

4.Type of gas being used and that shown on the rating label.

The Service Department at Empire Comfort Systems, Inc. may be contacted to assist in servicing furnace.

Servicing the Pilot and Main Burners, Pilot Orifice, and Main Burner Orifices: Disconnect the gas supply at the inlet to the control valve. Then remove the burner door to which the above components are attached.

S8600H INTERMITTENT IGNITION MODULE SPECIFICATIONS

Lockout timing is 90 seconds. Ignition timing is until pilot lights or lockout occurs.

Module shuts down and cuts power to gas control on flame failure. Gas control closes to provide 100 percent lockout on flame failure. Manual reset required.

ELECTRICAL RATINGS:

Voltage and frequency: 20.5 to 28.5V (24V nom.) 60 Hz.

Current rating: 0.2 A.

Valve contact ratings (at 24 Vac):

 

Run

Inrush

Pilot

1.0 A

10.0 A

Main

1.0 A

10.0 A

SPARK GENERATOR OUTPUT: 13kV peak at 25 pf load.

THERMOSTATANTICIPATOR SETTING: 0.2Aplus pilot valve rating plus main valve rating.

THERMOSTAT COMPATIBILITY: Standard models compatible with all open-close switch type 24 Vac thermostats capable of supplying rated voltage and current to the module.

AMBIENT TEMPERATURE RATING: Minus 40 F to plus 175 F (minus 40 C to plus 79 C).

RELATIVE HUMIDITY RATING: 5 to 90 percent RH at 95 F.

FLAME FAILURE RESPONSE TIME: 0.8 seconds at 1.0 uA flame current.

FLAME CURRENT: 1 uA, min.

CHECKOUT

Check out the gas control system:

1.At initial installation of the appliance.

2.As part of regular maintenance procedures.

3.As the first step in troubleshooting.

4.Any time work is done on the system.

STEP 1: Perform Visual Inspection.

A.With power off, make sure all wiring connections are clean and tight.

B.Turn on power to appliance and ignition module.

C.Open manual shutoff valves in the gas line to the appliance.

D.Do gas leak test ahead of gas control if piping has been disturbed.

Gas Leak Test: Paint pipe joints with rich soap and water solution. Bubbles indicate gas leak. Tighten joints to stop leak.

STEP 2: Review Normal Operating Sequence and Module Specifications.

STEP 3: Reset the Module.

A.Turn the thermostat to its lowest setting.

B.Wait one minute.

As you do Steps 4 and 5, watch for points where operation deviates from normal. Refer to Troubleshooting Chart to correct problem.

STEP 4: Check Safety Lockout Operation.

A.Turn gas supply off.

B.Set thermostat above room temperature to call for heat.

C.Watch for spark at pilot burner.

D.Time length of spark operation. Maximum spark time is 90 seconds.

E.Open manual gas cock and make sure no gas is flowing to pilot or main burner.

F.Set thermostat below room temperature and wait one minute before continuing.

STEP 5: Check Normal Operation.

A.Set thermostat above room temperature to call for heat.

B.Make sure pilot lights smoothly when gas reaches the pilot burner.

C.Make sure main burner lights smoothly without flashback. Make sure burner operates smoothly without floating or lifting.

D.If gas line has been disturbed, complete gas leak test.

Gas leak test: Paint gas control gasket edges and all pipe connections downstream of gas control, including pilot tubing connections, with rich soap and water solution. Bubbles indicate gas leaks. Tighten joints and screws or replace component to stop gas leak.

E.Turn thermostat below room temperature. Make sure main burner and pilot flames go out.

OPERATION

Module operation can be conveniently divided into two phases for S8600H. The phases are trial for ignition and main burner operation.

TRIAL FOR IGNITION

Pilot Ignition

Following call for heat (system start on S8600H), the module energizes the first main valve operator. The first main valve opens, which allows gas to flow to the pilot burner. At the same time, the electronic spark generator in the module produces a 13,000 volt spark pulse output (at 25 pf load). The voltage generates a spark at the igniter-sensor that lights the pilot.

If the pilot does not light, or the pilot flame current is not at least

1.0uA and steady, the module will not energize the second main valve and the main burner will not light.

21759-6-0608

Page 53

Page 53
Image 53
Empire Comfort Systems DVP42FP Intermittent Pilot Troubleshooting, S8600H Intermittent Ignition Module Specifications

DVP42FP, P)-2 specifications

Empire Comfort Systems has established itself as a leader in the heating and venting industry, providing innovative solutions that cater to modern home heating needs. One of their standout products is the Empire Comfort Systems DVP42FP,P)-2, a direct vent gas fireplace that seamlessly combines aesthetics, efficiency, and technology.

At the heart of the DVP42FP,P)-2 is its contemporary design, which enhances the ambiance of any living space. With a sleek glass front and a range of stylish finishes, this fireplace serves as a perfect centerpiece, embodying both function and fashion. The generous viewing area allows for an unobstructed view of the mesmerizing flames, creating a cozy atmosphere in any room.

This fireplace is engineered for efficiency and performance. With an impressive heating output, the DVP42FP,P)-2 can effectively warm spaces while consuming minimal fuel. It boasts a high-efficiency rating, ensuring that homeowners can enjoy the warmth without incurring high energy costs. The direct vent technology allows for a sealed combustion system that draws air from outside while expelling exhaust gases directly outdoors. This ensures that the air quality inside the home is maintained while providing optimal heating performance.

Ease of use is another hallmark of the DVP42FP,P)-2. It features an intuitive remote control system, allowing users to adjust the temperature and flame settings conveniently from anywhere in the room. This level of user-friendly control enhances the overall experience, making it easy to create the perfect environment.

Another notable characteristic of this model is its safety features. Equipped with safety screens and an auto shut-off feature, the DVP42FP,P)-2 is designed to offer peace of mind, allowing families to enjoy their fireplace without worries about safety.

Maintenance is straightforward with the DVP42FP,P)-2, thanks to its accessible design. Regular upkeep is minimal, allowing homeowners to spend more time enjoying the warmth and beauty of their fireplace rather than worrying about system maintenance.

In conclusion, the Empire Comfort Systems DVP42FP,P)-2 is a captivating, efficient, and technologically advanced direct vent gas fireplace. With its modern design, high efficiency, user-friendly controls, and robust safety features, it represents a wise investment for anyone looking to enhance their home's comfort and aesthetic appeal. Whether for a new build or a renovation, this fireplace stands out as a premier choice for discerning homeowners.