B) PIEZO IGNITOR OK BUT PILOT WILL STILL NOT LIGHT

Make sure all gas lines have

been connected with no

leaks.

Make sure that the gas is “ON” (NG) Natural gas and (LP) Propane tanks are full.

Make sure the appliance

service valve is in the “ON”

position.

SEE PAGE 4 FIGURE 3.

Test to make sure there is no

air in the gas line.

SEE PAGE 4 FIGURE 3.

Make sure that the valve has

not reset itself.

(All valves have an interlock

safety device.)

Make sure pilot injector is

not clogged.

Correct if necessary, test

for gas leaks in an approved manner.

Correct if necessary.

Turn service valve to the

“ON” position.

Use a match to see if air or gas comes from the pilot assembly.

Wait 60 seconds for the

safety to reset itself.

Clean the pilot injector if

necessary.

 

 

 

 

 

 