CHECKING THERMOPILE FOR PROPER VOLTAGE Place the leads of the multimeter on the TP/TH and TP terminals on the valve as shown.

190 mv DCWith the switch in the “ON” position, the readings should be approximately 190mV DC (this an average reading) or

greater for proper Thermopile operation.

The main burners may not come ON if the readings are

less than 145mV DC.

If a thermostat has been installed. Place the

ON/OFF/THERMO switch in the THERMO position; place the leads of the multimeter on the TP/TH and TH terminals on the valve or on the connections at the thermostat. MV reading should be higher than 190 mV DC for proper valve operation.

THESE READINGS SHOULD BE CONSTANT WITH NO

FLUCTUATION.

 

 

 

 

CHECKING

 

 

 

 

2 to 6mv DC

 

 

THERMOCOUPLE FOR

 

 

 

 

PROPER VOLTAGE

 

 

 

 

Place one lead from the

 

 

 

 

multimeter on the

 

 

 

 

thermocouple lead, and the

 

 

 

 

other lead from the

 

 

 

 

multimeter on the back of

 

 

 

 

the valve where the blue

 

 

 

 

wire is soldered to the valve.

 

 

 

 

These readings should be

 

 

 

 

between 8 and 16mV DC.

 

 

 

 

If these readings are 2 to 6

 

THERMOCOUPLE

 

 

 

mV DC, the Thermocouple

 

 

 

 

 

 

 

 

should be replaced

 

 

 

 

 

 

 

 

 

When using a S.I.T EUROSIT 630 SERIES gas valve, place

 

 

 

 

one lead from the multimeter on the thermocouple lead and

 

 

 

 

the other lead into the adapter located on the back of the

 

 

 

 

valve, there are two blue wire a inserted into this adapter.

 

 

 

 

 

 

 

 

 

 

 

Sherwood Industries Ltd.

ENVIRO

PAGE 6

 

 

 

 

 

 

Page 8
Image 8
Enviro C-10100 These Readings should be Constant with no Fluctuation, Proper Voltage, Checking, Thermocouple for