4)MAIN BURNERS WILL NOT STAY LIT

Make sure pilot flame engulfs

the thermopile and does

“NOT” have a yellow

luminous flame.

SEE PAGE 4 FIGURE 4.

Make sure millivolt readings from thermopile are constant.

Make sure all wiring is not damaged or broken and all connections are tight.

B-VENTED MODELS

Check spill switch.

Check to make sure the vent is

drafting properly.

Make sure all venting meets manufactures specifications as well as local gas and building code requirements.

Check chimney for blockage

or restriction.

Adjust pilot if necessary.

Check outlet gas pressure.

Check for clogged pilot

injector or blocked air inlet.

Using a multimeter check thermopile. If not constant replace thermopile.

Correct if necessary.

By pas spill switch.

If unit starts, replace spill

switch.

Check for spillage.

SEE PAGE 12.

Correct if necessary.

Correct if necessary.

 

 

 

 

 

 