Figure P

Section 8 - Troubleshooting/Maintenance

Prior to performing maintenance of any kind, lockout and tagout the electrical

power at both the facility source and the input circuit breaker. Under these condi- tions, entering the equipment enclosure will be classified as a Type 1 task under

SEMI S2-0200 guidelines. Power must be locked out and tagged out at both locations prior to entering the enclosure for maintenance purposes.

8.1.2.3EMO Has Been Activated - The front panel EMO pushbutton latches in a closed position once it has been depressed. Ensure that the EMO button has not been depressed by turning the button in the direction of the arrows and allowing it to spring back to its normal operating position. If the power conditioner is equipped with the external EMO option, further ensure that remote EMO buttons or connected external EMO circuits have not been activated. Once all EMO buttons and circuits have been verified, rotate the circuit breaker handle to the extreme counter-clockwise position and then rotate clockwise to the “On” position. If the circuit breaker once again trips immediately, contact the manufacturer for further instructions.

8.1.2.4Safety Interlocks Activated - Check both side panels of the power conditioner for proper instal- lation and secure fit. Both panels must be firmly in place and securely fastened with the quarter turn fasteners provided. A loose or improperly attached panel will allow the safety interlocks to activate and shunt trip the front panel circuit breaker. Once the panels have been checked, rotate the circuit breaker handle to the extreme counter-clockwise position and then rotate clockwise to the “On” position.

If the circuit breaker once again trips immediately, contact the manufac- turer for further instructions.

8.1.3TVSS Fault LEDs Illuminate

If one or more TVSS Fault LEDs illuminate, it is an indication that the TVSS components may be damaged. These components are protected by fuses. The TVSS module and it’s associated fuses are located inside

the power conditioner enclosure, on the right side below the isolation transformer as illustrated in Figure P to the right. The TVSS module itself is attached to the rear of the mounting panel. Three resistors are associated with the fuses. The resistors function as “pull up” resistors to light the front panel LEDs should one or more of the fuses open. The TVSS module, fuses, and resistors are accessed by removing one or both side panels as de- scribed in Section 5.3.

The fuses may be checked for continuity using an ordinary multi-meter. Open fuses may be replaced on site us- ing an Amptrap ATQ20, Time Delay, 10 kA IR, 500 VAC, 20A fuse or equivalent. Once the fuses have been replaced, replace the side panels as described in Section 6.1 taking care to reattach the grounding straps. Once completed, rotate the circuit breaker to the clockwise “On” position. If one or more of the TVSS Fault LEDs re- illuminate, the fuses have opened once again. This indicates that the TVSS element is damaged and requires replacement. Contact the manufacturer to order a replacement part.

Conditioned Power Center

31

Page 31
Image 31
ETA Systems SM5505 manual Tvss Fault LEDs Illuminate