Section 10 - Specifications

10.4 Output Voltage Fine Adjustment

IMPORTANT: ALL WORK TO BE DONE

BY A LICENSED ELECTRICIAN

-5%

Nominal +5%

-5%

Nominal +5%

-5%

Nominal +5%

TRANSFORMER SECONDARY

The output voltage of the transformer may be adjusted +5% from nominal using the taps shown above. First disconnect the power and all load equipment. After removing the side panels, move the wire from the “nominal” transformer tap to the desired adjustment tap to adjust output voltage up or down. Replace side panels. Then energize the transformer and check for proper desired voltage at output before reconnecting and energizing the load.

IMPORTANT NOTE: BE SURE TO ADJUST THE TAPS ON ALL THREE PHASES.

Conditioned Power Center

37

Page 37