Section 2 - Safety
Figure A

2.4 Safety Interlocks

This product incorporates a safety interlock circuit that functions as a secondary means of protection for personnel. Protective side panels and hazard warning labels provide primary protection. However, in the event one or more side panels are removed from the product prior to being de- energized, the safety interlock system will de-energize the power conditioner. The circuit consists of two safety interlock switches (one per each side access panel) located in the center of the top side frame of the power conditioner. The switches operate as a normally open circuit connected to the shunt trip coil of the input circuit breaker. See Figure A. Activating either of these safety

interlock switches causes a 24 VDC signal to energize the shunt trip coil of the breaker. The 24 VDC signal is derived from a low voltage, fused tap on the transformer secondary. The shunt trip circuit also uses stored energy from a capacitive circuit to ensure that the shunt trip mechanism will function even in the event of a power outage. The safety interlock switches are shown on the general circuit diagram found in subsection 10.1 of Section 10 of this manual.

If the power conditioner shunt trips as a result of removing the side panels, hazard- ous voltages will remain at the input voltage connection to the rear of the main cir- cuit breaker. Entering the enclosure under these conditions is classified as a Type 4 task under SEMI S2-0200 guidelines. This can be changed to a Type 1 task by disconnecting power at

the source before entering the enclosure.

2.5 Lockout/Tagout

 

 

The rotary handle of the main breaker is equipped with a

 

 

hinged center insert clearly identified with an arrow. The

 

 

rotary handle of the main breaker must be in the horizontal

 

 

position to proceed. See Figure B. Depress the insert on

 

 

the arrow on the left hand side causing the insert to extend

 

 

on the right revealing a slot to accommodate a locking

 

 

device as shown in Figure C. The lockout/tagout feature is

Figure B

Figure C

designed to prevent personnel from accidentally energizing

 

 

the power conditioner while maintenance, service or repair

 

 

is being performed. With the lockout/tagout engaged, hazardous voltages are still present at the rear of the input circuit breaker where input power feeds connect to the power conditioner. Entering the enclosure under these circumstances is classified as a Type 4 Task under SEMI S2-0200. Entering the enclosure may be classified as a Type 1 Task if power is disconnected from the power conditioner at the source.

Conditioned Power Center

9

Page 9
Image 9
ETA Systems SM5505 manual Safety Interlocks, Lockout/Tagout