8.1.7 Combustion test

UK/IRL

 

 

 

UK/IRL

 

8.1.7 Combustion test

8.1.6 Gas control block

A BS7967 combustion analysis check should be carried out using an

 

analyser to BS7927 positioned in the flue outlet.

 

A Ratio of CO/CO2 should be less than 0.01 within 30 minutes.

 

(100ppm CO per 1% CO2).

 

A reading of CO in the room centre should give a rise of less than

 

9ppm over ambient, peak reading.

BA

D CC

A Governor

fig. 26

BAdjusting screw pilot flame C Inlet pressure test point

DBurner pressure test point

38

 

 

 

39

 

 