Faber MISTY, SPECTRA NOVA Introduction, Safety And General Information, Uk/Irl, General safety

Models: CADRA NOVA MISTY FEELING SILENCE SPECTRA NOVA WHISPER

1 29
Download 29 pages 61.36 Kb
Page 3
Image 3
1. INTRODUCTION

UK/IRL

1. INTRODUCTION

Note: these instructions should be read carefully and retained for future reference.

Please leave these instructions with the user.

This guide is concerning the following types of appliances:

Widescreen interior:

Types Silence and Feeling

Roundscreen interior:

Type Misty

MV100 interior:

Type Whisper

MV110 interior:

Types Spectra Nova and Cadra Nova

Special features:

 

-Realistic flame and glow effect because of the "Log burner" technology.

-Room sealed appliance, inlet and outlet are led to the outside using a natural draught concentric pipe system (100 mm/150 mm) (no power fan required). No additional ventilation required.

-Air supply and flue-gases go to outside atmosphere through wall or roof. A maximum horizontal extension of 6 meters is possible.

-Remote Control option on all appliances.

-Meets the essential requirements of the European Gas Appliance Directive (GAD) and carries the CE mark.

UK/IRL

2.SAFETY AND GENERAL INFORMATION

Before installation, ensure that the local distribution conditions (identification of the type of gas and pressure) and the adjustment of the appliance are compatible.

This gas appliance is factory set and shall not be adjusted by the installer.

This appliance does not contain any component manufactured from asbestos or any asbestos related products.

The pilot and flame sensing device fitted to this fire is also a safety device. If for any reason any part of the pilot assembly is to be replaced the entire assembly including the pilot burner, thermocouple, electrode and injector must be exchanged complete for a pilot assembly from the original manufacturer only.

Ventilation

This appliance is room-sealed and doesn't require purpose provided ventilation.

2.1 General safety

It is the law in the UK that all gas appliances, are installed by a competent person in accordance with the Gas Safety (Installation and Use) Regulations (as amended), the relevant British Standards for Installation work, Building Regulations, Codes of Practice and the manufacturers instructions.

The installation should also be carried out in accordance with the following where relevant:

BS5871 Part1

BS5440 Parts 1 & 2

BS1251.

Building Regulations Document J (as applicable).

2

 

 

 

3

 

 