FS-8700-49_Data_Aire_DAP

 

 

Page 42 of 48

 

 

 

 

 

 

 

 

 

 

 

 

 

Location in

Location in Data

 

 

 

 

 

 

 

Data Array

Array (Absolute

 

 

 

 

Byte

Bit

Relative

(Absolute

Offset) Each set

046, 048 and 049 Units

DAP 80 Units

 

 

 

Offset

Offset) Each

of 8 alarms

 

 

 

 

 

 

 

alarm stored as

stored as a

 

 

 

 

 

 

 

a separate bit

byte*

 

 

 

 

 

 

 

 

 

High Pressure Failure

Humidifier problem:

 

0

4

4

77

43:00

check water

 

Compressor No. 4

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

0

5

5

78

43:01

High Pressure Warning

Low voltage

 

Compressor No. 1

warning: check unit

 

 

 

 

 

 

 

0

6

6

79

43:02

High Pressure Warning

Firestat alarm: unit

 

Compressor No. 2

shutdown

 

 

 

 

 

 

 

0

7

7

80

43:03

High Pressure Warning

Compressor short

 

Compressor No. 3

cycle warning

 

 

 

 

 

 

 

1

0

8

81

46:00

High Pressure Warning

Power problem or

 

Compressor No. 4

unit restart

 

 

 

 

 

 

 

1

1

9

82

46:01

Low Pressure Failure

Humidity sensor

 

Compressor No. 1

problem

 

 

 

 

 

 

 

1

2

10

83

46:02

Low Pressure Failure

Temperature sensor

 

Compressor No. 2

problem

 

 

 

 

 

 

 

1

3

11

84

46:03

Low Pressure Failure

Scheduled

 

Compressor No. 3

maintenance due

 

 

 

 

 

 

 

 

 

 

 

 

Low Pressure Failure

High pressure C1:

 

1

4

12

85

44:04

Manual reset

 

Compressor No. 4

 

 

 

 

 

 

required

 

 

 

 

 

 

 

 

 

 

 

 

 

No Air Flow, Check Belt

Low pressure C1:

 

1

5

13

86

44:05

Manual reset

 

and motor

 

 

 

 

 

 

required

 

 

 

 

 

 

 

 

 

 

 

 

 

Change Filters, High

High pressure C2:

 

1

6

14

87

44:06

Manual reset

 

Pressure Drop

 

 

 

 

 

 

required

 

 

 

 

 

 

 

 

 

 

 

 

 

Local Alarm. See Tag

Low pressure C2:

 

1

7

15

88

44:07

Manual reset

 

inside Door

 

 

 

 

 

 

required

 

 

 

 

 

 

 

 

2

0

16

89

45:00

Manual Override, service

Smoke detector: unit

 

or emergency

shutdown

 

 

 

 

 

 

 

2

1

17

90

45:01

Humidifier Failure, Check

No water flow: check

 

water pressure

pump

 

 

 

 

 

 

 

 

 

 

 

 

No water flow. Check

Discharge

 

2

2

18

91

45:02

temperature sensor

 

glycol pump.

 

 

 

 

 

 

problem

 

 

 

 

 

 

 

 

2

3

19

92

45:03

Smoke detected, located

High temperature

 

inside unit

warning

 

 

 

 

 

 

 

2

4

20

93

45:04

Fire Stat Tripped, Location

Low temperature

 

inside unit

warning

 

 

 

 

 

 

 

2

5

21

94

45:05

Standby pump on, check

High humidity

 

glycol pump

warning

 

 

 

 

 

 

 

2

6

22

95

45:06

Low voltage warning,

Low humidity

 

check unit

warning

 

 

 

 

 

 

 

 

 

 

 

 

Water detected in under

Fan motor overload:

 

2

7

23

96

45:07

check motor

 

 

 

 

 

 

floor area

amperage

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Page 42
Image 42
FieldServer FS-8704-49 instruction manual FS-8700-49DataAireDAP