FS-8700-49_Data_Aire_DAP

 

Page 24 of 48

 

 

 

 

 

 

Note 1:mode: 2' bit definitions:

 

Note 2: hold: 2' bit definitions:

 

0X01

Unit is in centigrade mode

 

0X01

needed cooling is inhibited

 

0X02

RFU , always 1

 

0X02

needed heatingg is inhibited

 

0X04

RFU , always 1

 

0X04

needed humidification is inhibited

 

0X08

Unit is dehumidifying

 

0X08

needed dehumidification is inhibited

 

0X10

Unit is humidifying

 

0X10

not used

 

0X20

Energy save is active

 

0X20

not used

 

0X40

not used

 

0X40

Network"standby" inhibit is active

 

0X80

not used

 

0X80

Network"off" inhibit is active

 

Note 2: errors: 7*2' bit definitions:

 

 

 

00

Manual override:check bypass switches

errors[0], bit 0x01

 

01

water detected under floor

 

errors[0], bit 0x02

 

02

No air flow, check belt and motor

errors[0], bit 0x04

 

03

dirty filter: check filter

 

errors[0], bit 0x08

 

04

Humidifier problem: check water pressure

errors[0], bit 0x10

 

05

Low voltage warning

 

errors[0], bit 0x20

 

06

Firestat alarm, unit shutdown

 

errors[0], bit 0x40

 

07

compressor short cycle

 

errors[0], bit 0x80

 

08

power problem or unit restart

 

errors[1], bit 0x01

 

09

humidity sensor problem

 

errors[1], bit 0x02

 

10

temperature sensor problem

 

errors[1], bit 0x04

 

11

schedule maintenance due

 

errors[1], bit 0x08

 

12

high presure C1: manual reset

 

errors[1], bit 0x10

 

13

low presure C1: auto reset

 

errors[1], bit 0x20

 

14

high presure C2: manual reset

 

errors[1], bit 0x40

 

15

low presure C2: auto reset

 

errors[1], bit 0x80

 

16

smoke detector: unit shutdown

 

errors[2], bit 0x01

 

17

No water flow :check pump

 

errors[2], bit 0x02

 

18

Discharge temperature sensor problem

errors[2], bit 0x04

 

19

High Temperature warning

 

errors[2], bit 0x08

 

20

Low temperature warning

 

errors[2], bit 0x10

 

21

High humidity warning

 

errors[2], bit 0x20

 

22

low humidity warning

 

errors[2], bit 0x40

 

23

Fan motor overload: check motor amperage

errors[2], bit 0x80

 

24

Local alarm 1: see tag inside door

errors[3], bit 0x01

 

25

Local alarm 2: see tag inside door

errors[3], bit 0x02

 

26

Local alarm 3: see tag inside door

errors[3], bit 0x04

 

27

Local alarm 4: see tag inside door

errors[3], bit 0x08

 

28

Standby Pump on: check primary pump

errors[3], bit 0x10

 

29

UPS power on: check primary power

errors[3], bit 0x20

 

30

Custom message on optional input 1

errors[3], bit 0x40

 

31

Custom message on optional input 2

errors[3], bit 0x80

 

32

Custom message on optional input 3

errors[4], bit 0x01

 

33

Custom message on optional input 4

errors[4], bit 0x02

 

34

Humidification inhibited

 

errors[4], bit 0x04

 

35

Reheat inhibited

 

errors[4], bit 0x08

 

36

Reheat and humidification inhibited

errors[4], bit 0x10

 

37

Discharge air temperature limit

 

errors[4], bit 0x20

 

38

Reheat mode during dehumidication

errors[4], bit 0x40

 

39

Manual override:check bypass switches

errors[4], bit 0x80

 

40

High condensate water level

 

errors[5], bit 0x01

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Page 24
Image 24
FieldServer FS-8704-49 instruction manual FS-8700-49DataAireDAP