FS-8700-49_Data_Aire_DAP

 

 

Page 45 of 48

 

 

 

 

 

 

 

 

 

 

Location in Data Array

 

 

 

 

Relative

 

 

(Absolute Offset) Each alarm

Alarm / Bit Descriptions

Byte

Bit

 

 

stored as a separate bit

 

 

 

 

Offset

 

 

 

 

 

 

 

 

 

550

Local alarm #2: See tag inside door

1

 

6

14

 

 

551

Low pressure problem module #1

1

 

7

15

 

 

552

Low pressure problem module #2

2

 

0

16

 

 

553

Low pressure problem module #3

2

 

1

17

 

 

554

Low return temperature warning

2

 

2

18

 

 

555

Low supply temperature warning

2

 

3

19

 

 

556

Low voltage warning: check unit

2

 

4

20

 

 

557

Scheduled normal maintenance due

2

 

5

21

 

 

558

Manual override: compressor

2

 

6

22

 

 

559

Manual override: check bypass switches

2

 

7

23

 

 

560

No chilled water flow module #1

3

 

0

24

 

 

561

No chilled water flow module #2

3

 

1

25

 

 

562

No chilled water flow module #3

3

 

2

26

 

 

563

No condenser water flow

3

 

3

27

 

 

564

Power problem or restart

3

 

4

28

 

 

565

Return temperature sensor problem

3

 

5

29

 

 

566

compressor short cycle warning

3

 

6

30

 

 

567

Standby pump on: Check primary pump

3

 

7

31

 

 

568

Supply temperature sensor problem

4

 

0

32

 

 

569

Unit on total standby

4

 

1

33

 

 

570

Under floor water detected

4

 

2

34

 

 

571

N/A

4

 

3

35

 

 

572

N/A

4

 

4

36

 

 

573

N/A

4

 

5

37

 

 

574

N/A

4

 

6

38

 

 

575

N/A

4

 

7

39

 

 

576

N/A

5

 

0

40

 

 

577

N/A

5

 

1

41

 

 

578

N/A

5

 

2

42

 

 

579

N/A

5

 

3

43

 

 

580

N/A

5

 

4

44

 

 

581

N/A

5

 

5

45

 

 

582

N/A

5

 

6

46

 

 

583

N/A

5

 

7

47

 