Models: FS-8704-49

1 48
Download 48 pages 32.01 Kb
Page 43
Image 43

FS-8700-49_Data_Aire_DAP

 

 

Page 43 of 48

 

 

 

 

 

 

 

 

 

 

 

 

 

Location in

Location in Data

 

 

 

 

 

 

 

Data Array

Array (Absolute

 

 

 

 

Byte

Bit

Relative

(Absolute

Offset) Each set

046, 048 and 049 Units

DAP 80 Units

 

 

 

Offset

Offset) Each

of 8 alarms

 

 

 

 

 

 

 

alarm stored as

stored as a

 

 

 

 

 

 

 

a separate bit

byte*

 

 

 

 

3

0

24

97

46:00

Low air temperature

Local alarm #1: See

 

warning

tag inside door

 

 

 

 

 

 

 

3

1

25

98

46:01

High air temperature

Local alarm #2: See

 

warning

tag inside door

 

 

 

 

 

 

 

3

2

26

99

46:02

Low Humidity warning

Local alarm #3: See

 

tag inside door

 

 

 

 

 

 

 

 

3

3

27

100

46:03

High Humidity warning

Local alarm #4: See

 

tag inside door

 

 

 

 

 

 

 

 

3

4

28

101

46:04

Low chilled-water-in alarm

Standby pump on:

 

check primary pump

 

 

 

 

 

 

High chilled-water-in

UPS power on:

 

3

5

29

102

46:05

check main power

 

alarm

 

 

 

 

 

 

supply

 

 

 

 

 

 

 

 

3

6

30

103

46:06

Low chilled-water-out

Custom message on

 

alarm

optional input #1

 

 

 

 

 

 

 

3

7

31

104

46:07

High chilled-water-out

Custom message on

 

alarm

optional input #2

 

 

 

 

 

 

 

4

0

32

105

47:00

High or Low limits

Custom message on

 

misadjusted

optional input #3

 

 

 

 

 

 

 

4

1

33

106

47:01

Air temperature sensor

Custom message on

 

error

optional input #4

 

 

 

 

 

 

 

4

2

34

107

47:02

Humidity sensor error

Humidification

 

Inhibited

 

 

 

 

 

 

 

 

4

3

35

108

47:03

Discharge air sensor error

Reheat inhibited

 

 

 

 

 

 

No communications with

Reheat and

 

4

4

36

109

47:04

humidification

 

 

 

 

 

 

temp/humid module

inhibited

 

 

 

 

 

 

 

 

 

 

 

 

 

No communications with

Discharge air

 

4

5

37

110

47:05

temperature limit

 

 

 

 

 

 

LCD module

(just a condition)

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm network

Reheat mode during

 

4

6

38

111

47:06

dehumidification

 

communications failure

 

 

 

 

 

 

(just a condition)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual Override:

 

4

7

39

112

47:07

AC Power or controller

Check bypass

 

restart

switches (DAPII ver

 

 

 

 

 

 

 

 

 

 

 

 

 

5.1 and later)

 

5

0

40

113

48:00

Network doppelganger

N/A

 

error

 

 

 

 

 

 

 

 

 

5

1

41

114

48:01

Incompatible Fahrenheit /

N/A

 

 

 

 

 

 

centigrade mode

 

 

 

5

2

42

115

48:02

Schedule normal

N/A

 

maintenance due

 

 

 

 

 

 

 

 

 

5

3

43

116

48:03

compressor short cycle

N/A

 

warning

 

 

 

 

 

 

 

 

 

5

4

44

117

48:04

Fan motor overload,

N/A

 

check motor amperage

 

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com