FS-8700-49_Data_Aire_DAP

Page 8 of 48

4.2.Client Side Connection Descriptions

Connections

 

 

Column Title

Function

Legal Values

 

This is the FieldServer port

P1-P8, R1-R21

Port

connected to the DART’s RS-

(P1-P8) requires 232/485

 

232 port.

converter.

 

The return loop from the DAP

P1-P8, R1-R21

Secondary_Port*

devices is connected to this

(R1-R2) requires 232/485

port. (Loop connected to Tx+

 

converter.

 

& Tx- terminals.

 

 

Baud*

Specify baud rate

2400/96002 (Vendor

Limitation)

 

 

Parity*

Specify parity

None

Data_Bits*

Specify data bits

8

 

 

 

Stop_Bits*

Specify stop bits

1

 

 

 

Protocol

Specify protocol used. Either

DAP, Daire

keyword may be used.

 

 

Handshaking*

Specify hardware

None

handshaking

 

 

Poll Delay*

Time between internal polls

0-32000s, 1s

 

 

 

Example

//Client Side Connections

Connections

Port,

Secondary Port,

Protocol,

Baud,

Parity,

Data_Bits,

Stop_Bits,

Poll_Delay

R1,

R2,

DAP,

2400,

None,

8,

1,

0.100s

Use this port identifier in the client side node configuration described in Section 4.3.

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware. 2DAP V9.5 or later supports 9600

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com