| Page 8 of 48 |
4.2.Client Side Connection Descriptions
Connections |
|
| |
Column Title | Function | Legal Values | |
| This is the FieldServer port | ||
Port | connected to the DART’s RS- | ||
| 232 port. | converter. | |
| The return loop from the DAP | ||
Secondary_Port* | devices is connected to this | ||
port. (Loop connected to Tx+ | |||
| converter. | ||
| & Tx- terminals. | ||
|
| ||
Baud* | Specify baud rate | 2400/96002 (Vendor | |
Limitation) | |||
|
| ||
Parity* | Specify parity | None | |
Data_Bits* | Specify data bits | 8 | |
|
|
| |
Stop_Bits* | Specify stop bits | 1 | |
|
|
| |
Protocol | Specify protocol used. Either | DAP, Daire | |
keyword may be used. | |||
|
| ||
Handshaking* | Specify hardware | None | |
handshaking | |||
|
| ||
Poll Delay* | Time between internal polls | ||
|
|
|
Example
//Client Side Connections
Connections
Port, | Secondary Port, | Protocol, | Baud, | Parity, | Data_Bits, | Stop_Bits, | Poll_Delay |
R1, | R2, | DAP, | 2400, | None, | 8, | 1, | 0.100s |
Use this port identifier in the client side node configuration described in Section 4.3.
1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware. 2DAP V9.5 or later supports 9600
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408)