12Installation instructions
Additional electrical requirements
Electrical installation must be carried out only by a licensed electrician.
The cooktop MUST be connected to the proper electrical voltage and frequency as specified:
Model | Rated power | Required power supply |
CE244C | 5.9kW (4.4kW) | 240V~,25A, 60Hz (208V~, 21.3A, 60Hz) |
CE365D | 8.4kW (6.5kW) | 240V~,35A, 60Hz (208V~, 30.3A, 60Hz) |
This appliance must be connected to a grounded, metallic permanent wiring system or a ground connector should be connected to the ground terminal or wire lead on the cooktop.
This appliance is manufactured with a
Warning: improper connection of aluminum house wiring to copper leads can result in an electrical hazard or fire. Use only connectors designed for joining copper to aluminum and follow the manufacturer’s recommended procedure.
Connect the cooktop with copper wire only.
The flexible (4’) armored cable should be connected directly to the junction box. Do not cut the conduit.
A CSA or
Do not have a fuse in the grounding or neutral circuit. A time delay fuse or circuit breaker is recommended.
Connect directly to the fused disconnect (or circuit breaker box) through flexible, armored or
If codes permit and a separate grounding wire is used, it is recommended that a qualified electrician determine that the grounding path and wire gauge are in accordance with local codes.