Installation instructions 13
Converting to a different gas type
Gas regulator
For use with a gas pressure regulator as shown below. The regulator supplied can be set for
either LP Gas or Natural Gas.
| Cooktop | |
| To Cooktop | |
| Regulator | |
| Solid or Flexible | |
| Connector | |
Pressure | ||
Regulator | ||
shows | Valve | |
Direction of | Pipe Stub from | |
Gas Flow | ||
House supply | ||
|
Converting the regulator between NG & LP
1Unscrew the cap from the regulator.
2Check the orientation of the plastic conversion plug, and if necessary, unscrew, turn over and screw back in (wide section away from cap for LP and against cap for NG - see diagram below for appropriate orientation).
3Replace regulator cap.
4Test gas pressure (test point provision on side of regulator). When converting the regulator for different settings, the function of the regulator must be checked at a pressure at least 1” WC (0.036 psi) above the specified manifold pressure.
LP | NG |