Wiring Connections

! WARNING

Serious or fatal electrical shock may result from failure to connect the motor, the SubDrive300, metal plumbing and all other metal near the motor, or cable to the power supply ground terminal, using wire no smaller than motor cable wires. To reduce risk of electrical shock, disconnect power before working on or around the water system.

Do not use motor in swimming areas.

1.Verify that the power has been shut off at the main breaker.

2.Verify that the dedicated branch circuit for the SubDrive300 is equipped with a properly-sized circuit breaker. Refer to Table 2 (Page 13) for minimum breaker size.

3.Use the appropriate strain relief or conduit connectors. Type B liquid tight fittings are recommended for maximum weather protection.

4.Remove the SubDrive300 lid.

5.Feed the motor leads through the opening on the bottom right side of the unit and connect them to the terminal block positions marked GND (Green ground wire), Red, Yellow and Black (Figure 2).

SW1

SW2

PRESSURE

NO

NO

SENSOR

SHUT-OFF

 

 

RELAY

 

 

 

COM

PFC INV

FAN FAN

Output to Motor

Red Yel Blk

(Brn) (Blue) (Blk)

(Output)

Figure 2: Motor Lead Connections