COMPONENTS TESTING (Continued)

COMPONENTS TESTING (Continued)

EQ08 SYSTEM CONTROL SWITCH - TEST

“EQ08” SYSTEM CONTROL SWITCH – TEST

Turn knob to phase of switch to be tested. There must be continuity as follows:

1.“Fan Only” Position – between terminals “MS” and “H”

2.“Hi Cool” Position – between terminals “L1” and “C” and “MS” and “H”

3.“Low Cool” Position – between terminals “L1” and “C” and “MS” and “LO”

4.“Low Heat” Position – between terminals “L2” and “2” and “MS” and “LO”

5.“Hi Heat” Position – between terminals “L2” and “2” and “MS” and “H”

 

 

L1

 

System Control Switch

 

 

(EQ Models)

B1

 

 

MS

L2

H C

LO2

THERMOSTAT (“EQ08” Models) (See Figure 17)

This thermostat is single pole-double throw, cross ambient with a range of 60° to 92°F and a differential of ±2°F. Terminal “2” is common.

Thermostat

(EQ Model)

EQ08 SYSTEM CONTROL SWITCH - TESTWARNING

ELECTRIC SHOCK HAZARD

Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.

TEST:

1.Remove leads from thermostat.

2.Turn thermostat knob clockwise to its coldest position.

3.Test for continuity between the two terminals. Contacts should be closed.

4.Turn thermostat knob counterclockwise to its warmest position.

5.Test for continuity - contacts should be open.

NOTE: The thermostat must be within the temperature range listed to open and close.

To maintain the comfort level desired, a cross ambient type thermostat is used. The thermostat has a range from 60° ±2°F to 92° ±3°F. The thermostat bulb is positioned in front of the evaporator coil to sense the return air temperature. Thermostat malfunction or erratic operation is covered in the troubleshooting section of this manual.

TEST:

Cooling/Heating Models: Remove wires from thermostat and check continuity between terminal “2” (common) and “3” for cooling. Check between terminals “2” (common) and “1” for heating. Also check that contacts in thermostat open after placing in either position. NOTE: Temperature must be within range listed to check thermostat. Refer to the troubleshooting section in this manual for additional information on thermostat testing.

THERMOSTAT ADJUSTMENT

No attempt should be made to adjust thermostat. Due to the sensitivity of the internal mechanism and the sophisticated equipment required to check the calibration, it is suggested that the thermostat be replaced rather than calibrated. Thermostat bulb must be straight to insure proper performance.

Thermostat

THERMOSTAT BULB LOCATION

The position of the bulb is important in order for the thermostat to function properly. The bulb of the thermostat should be located approximately 45° to a maximum of 60° from horizontal. Also, do not allow the thermostat bulb to touch the evaporator coil. (See Figures 17 and 18)

Thermostat Bulb Location

(EQ Model)

Thermostat sensor holder 020 to be positioned between the 4th and 5th and 6th and 7th rows of tubes from the bottom of the coil at dimension shown

14

Page 15
Image 15